⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.57V (2.97%)
Voltage at Load End118.9 VLoss: 1.08 V (757.0 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A526.84 V (439.03%)0.0 V869.03 V (724.19%)368784.6 WDrop/Amp High
12 AWG3.31 mm²20 A331.06 V (275.89%)0.0 V546.1 V (455.08%)231743.8 WDrop/Amp High
10 AWG5.26 mm²30 A208.33 V (173.61%)0.0 V343.65 V (286.37%)145831.2 WDrop/Amp High
8 AWG8.37 mm²50 A130.92 V (109.1%)0.0 V215.96 V (179.97%)91645.4 WDrop/Amp High
6 AWG13.3 mm²65 A82.39 V (68.66%)37.6 V135.91 V (113.26%)57674.6 WDrop/Amp High
4 AWG21.15 mm²85 A51.81 V (43.18%)68.2 V85.47 V (71.22%)36268.2 WDrop/Amp High
3 AWG26.67 mm²100 A41.09 V (34.24%)78.9 V67.78 V (56.48%)28761.6 WDrop/Amp High
2 AWG33.62 mm²115 A32.59 V (27.16%)87.4 V53.77 V (44.8%)22815.9 WDrop/Amp High
1 AWG42.41 mm²130 A25.84 V (21.53%)94.2 V42.62 V (35.52%)18087.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.49 V (17.07%)99.5 V33.79 V (28.16%)14340.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.25 V (13.54%)103.7 V26.81 V (22.34%)11375.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.89 V (10.74%)107.1 V21.26 V (17.72%)9023.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.22 V (8.52%)109.8 V16.86 V (14.05%)7155.5 WDrop/Amp High
250 kcmil126.7 mm²255 A8.65 V (7.21%)111.4 V14.27 V (11.89%)6054.2 WDrop/Amp High
300 kcmil152.0 mm²285 A7.21 V (6.01%)112.8 V11.89 V (9.91%)5046.5 WDrop/Amp High
350 kcmil177.3 mm²310 A6.18 V (5.15%)113.8 V10.2 V (8.5%)4326.4 WDrop/Amp High
400 kcmil202.7 mm²335 A5.41 V (4.51%)114.6 V8.92 V (7.43%)3784.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.32 V (3.6%)115.7 V7.13 V (5.94%)3027.1 WDrop/Amp High
600 kcmil304.0 mm²420 A3.6 V (3.0%)116.4 V5.95 V (4.96%)2523.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.88 V (2.4%)117.1 V4.76 V (3.96%)2018.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.16 V (1.8%)117.8 V3.57 V (2.97%)1513.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 120 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.08V (0.9%) and delivers 118.9V at the load.

What size aluminum wire is required for 700 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.57V (2.97%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.