🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 60 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.45%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.78V (1.49%)
Voltage at Load End119.5 VLoss: 0.54 V (378.4 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 60 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A263.42 V (219.51%)0.0 V434.52 V (362.1%)184392.3 WDrop/Amp High
12 AWG3.31 mm²20 A165.53 V (137.94%)0.0 V273.05 V (227.54%)115871.9 WDrop/Amp High
10 AWG5.26 mm²30 A104.17 V (86.8%)15.8 V171.82 V (143.19%)72915.6 WDrop/Amp High
8 AWG8.37 mm²50 A65.46 V (54.55%)54.5 V107.98 V (89.98%)45822.7 WDrop/Amp High
6 AWG13.3 mm²65 A41.2 V (34.33%)78.8 V67.95 V (56.63%)28837.3 WDrop/Amp High
4 AWG21.15 mm²85 A25.91 V (21.59%)94.1 V42.73 V (35.61%)18134.1 WDrop/Amp High
3 AWG26.67 mm²100 A20.54 V (17.12%)99.5 V33.89 V (28.24%)14380.8 WDrop/Amp High
2 AWG33.62 mm²115 A16.3 V (13.58%)103.7 V26.88 V (22.4%)11408.0 WDrop/Amp High
1 AWG42.41 mm²130 A12.92 V (10.77%)107.1 V21.31 V (17.76%)9043.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.24 V (8.54%)109.8 V16.9 V (14.08%)7170.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.13 V (6.77%)111.9 V13.4 V (11.17%)5687.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.45 V (5.37%)113.6 V10.63 V (8.86%)4511.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.11 V (4.26%)114.9 V8.43 V (7.03%)3577.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.32 V (3.6%)115.7 V7.13 V (5.94%)3027.1 WDrop/Amp High
300 kcmil152.0 mm²285 A3.6 V (3.0%)116.4 V5.95 V (4.96%)2523.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.09 V (2.58%)116.9 V5.1 V (4.25%)2163.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.7 V (2.25%)117.3 V4.46 V (3.72%)1892.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.16 V (1.8%)117.8 V3.57 V (2.97%)1513.6 WDrop/Amp High
600 kcmil304.0 mm²420 A1.8 V (1.5%)118.2 V2.97 V (2.48%)1261.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.44 V (1.2%)118.6 V2.38 V (1.98%)1009.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.08 V (0.9%)118.9 V1.78 V (1.49%)756.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 60 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 60 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.54V (0.45%) and delivers 119.5V at the load.

What size aluminum wire is required for 700 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.78V (1.49%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.