🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.38%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.49V (1.24%)
Voltage at Load End119.5 VLoss: 0.45 V (315.4 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A219.51 V (182.93%)0.0 V362.1 V (301.75%)153660.2 WDrop/Amp High
12 AWG3.31 mm²20 A137.94 V (114.95%)0.0 V227.54 V (189.62%)96559.9 WDrop/Amp High
10 AWG5.26 mm²30 A86.8 V (72.34%)33.2 V143.19 V (119.32%)60763.0 WDrop/Amp High
8 AWG8.37 mm²50 A54.55 V (45.46%)65.4 V89.98 V (74.99%)38185.6 WDrop/Amp High
6 AWG13.3 mm²65 A34.33 V (28.61%)85.7 V56.63 V (47.19%)24031.1 WDrop/Amp High
4 AWG21.15 mm²85 A21.59 V (17.99%)98.4 V35.61 V (29.68%)15111.7 WDrop/Amp High
3 AWG26.67 mm²100 A17.12 V (14.27%)102.9 V28.24 V (23.53%)11984.0 WDrop/Amp High
2 AWG33.62 mm²115 A13.58 V (11.32%)106.4 V22.4 V (18.67%)9506.6 WDrop/Amp High
1 AWG42.41 mm²130 A10.77 V (8.97%)109.2 V17.76 V (14.8%)7536.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.54 V (7.11%)111.5 V14.08 V (11.73%)5975.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.77 V (5.64%)113.2 V11.17 V (9.31%)4739.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.37 V (4.48%)114.6 V8.86 V (7.38%)3759.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.26 V (3.55%)115.7 V7.03 V (5.85%)2981.5 WDrop/Amp High
250 kcmil126.7 mm²255 A3.6 V (3.0%)116.4 V5.94 V (4.95%)2522.6 WDrop/Amp High
300 kcmil152.0 mm²285 A3.0 V (2.5%)117.0 V4.96 V (4.13%)2102.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.58 V (2.15%)117.4 V4.25 V (3.54%)1802.7 WDrop/Amp High
400 kcmil202.7 mm²335 A2.25 V (1.88%)117.7 V3.72 V (3.1%)1576.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.8 V (1.5%)118.2 V2.97 V (2.48%)1261.3 WDrop/Amp High
600 kcmil304.0 mm²420 A1.5 V (1.25%)118.5 V2.48 V (2.06%)1051.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.2 V (1.0%)118.8 V1.98 V (1.65%)841.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.9 V (0.75%)119.1 V1.49 V (1.24%)630.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 50 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.45V (0.38%) and delivers 119.5V at the load.

What size aluminum wire is required for 700 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.49V (1.24%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.