🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.3V (9.29%)
Voltage at Load End233.2 VLoss: 6.76 V (4730.8 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3292.72 V (1371.97%)0.0 V5431.45 V (2263.1%)2304903.5 WDrop/Amp High
12 AWG3.31 mm²20 A2069.14 V (862.14%)0.0 V3413.12 V (1422.13%)1448398.5 WDrop/Amp High
10 AWG5.26 mm²30 A1302.06 V (542.53%)0.0 V2147.8 V (894.92%)911444.7 WDrop/Amp High
8 AWG8.37 mm²50 A818.26 V (340.94%)0.0 V1349.75 V (562.4%)572783.7 WDrop/Amp High
6 AWG13.3 mm²65 A514.95 V (214.56%)0.0 V849.43 V (353.93%)360466.1 WDrop/Amp High
4 AWG21.15 mm²85 A323.82 V (134.93%)0.0 V534.16 V (222.57%)226676.1 WDrop/Amp High
3 AWG26.67 mm²100 A256.8 V (107.0%)0.0 V423.6 V (176.5%)179760.0 WDrop/Amp High
2 AWG33.62 mm²115 A203.71 V (84.88%)36.3 V336.03 V (140.01%)142599.6 WDrop/Amp High
1 AWG42.41 mm²130 A161.49 V (67.29%)78.5 V266.39 V (110.99%)113044.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A128.04 V (53.35%)112.0 V211.21 V (88.0%)89628.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A101.57 V (42.32%)138.4 V167.54 V (69.81%)71098.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A80.57 V (33.57%)159.4 V132.9 V (55.37%)56395.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A63.89 V (26.62%)176.1 V105.39 V (43.91%)44722.0 WDrop/Amp High
250 kcmil126.7 mm²255 A54.06 V (22.52%)185.9 V89.17 V (37.15%)37839.0 WDrop/Amp High
300 kcmil152.0 mm²285 A45.06 V (18.77%)194.9 V74.33 V (30.97%)31540.8 WDrop/Amp High
350 kcmil177.3 mm²310 A38.63 V (16.1%)201.4 V63.72 V (26.55%)27040.0 WDrop/Amp High
400 kcmil202.7 mm²335 A33.79 V (14.08%)206.2 V55.73 V (23.22%)23651.7 WDrop/Amp High
500 kcmil253.4 mm²380 A27.03 V (11.26%)213.0 V44.58 V (18.58%)18919.5 WDrop/Amp High
600 kcmil304.0 mm²420 A22.53 V (9.39%)217.5 V37.16 V (15.48%)15770.4 WDrop/Amp High
750 kcmil380.0 mm²475 A18.02 V (7.51%)222.0 V29.73 V (12.39%)12616.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.52 V (5.63%)226.5 V22.3 V (9.29%)9461.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 750 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.76V (2.81%) and delivers 233.2V at the load.

What size aluminum wire is required for 700 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.3V (9.29%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.