🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 3.0%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.6V (9.9%)
Voltage at Load End201.8 VLoss: 6.25 V (7569.3 W)
Power & Breaker (125%)252.19 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3041.68 V (1462.35%)0.0 V5017.36 V (2412.19%)3687845.5 WDrop/Amp High
12 AWG3.31 mm²20 A1911.39 V (918.94%)0.0 V3152.9 V (1515.82%)2317437.7 WDrop/Amp High
10 AWG5.26 mm²30 A1202.8 V (578.27%)0.0 V1984.05 V (953.87%)1458311.5 WDrop/Amp High
8 AWG8.37 mm²50 A755.88 V (363.4%)0.0 V1246.85 V (599.45%)916453.8 WDrop/Amp High
6 AWG13.3 mm²65 A475.69 V (228.7%)0.0 V784.67 V (377.24%)576745.8 WDrop/Amp High
4 AWG21.15 mm²85 A299.13 V (143.81%)0.0 V493.43 V (237.23%)362681.7 WDrop/Amp High
3 AWG26.67 mm²100 A237.22 V (114.05%)0.0 V391.3 V (188.13%)287616.0 WDrop/Amp High
2 AWG33.62 mm²115 A188.18 V (90.47%)19.8 V310.41 V (149.24%)228159.4 WDrop/Amp High
1 AWG42.41 mm²130 A149.18 V (71.72%)58.8 V246.08 V (118.31%)180870.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A118.28 V (56.86%)89.7 V195.1 V (93.8%)143404.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A93.83 V (45.11%)114.2 V154.77 V (74.41%)113758.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A74.42 V (35.78%)133.6 V122.76 V (59.02%)90233.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A59.02 V (28.37%)149.0 V97.35 V (46.8%)71555.2 WDrop/Amp High
250 kcmil126.7 mm²255 A49.93 V (24.01%)158.1 V82.37 V (39.6%)60542.4 WDrop/Amp High
300 kcmil152.0 mm²285 A41.62 V (20.01%)166.4 V68.66 V (33.01%)50465.3 WDrop/Amp High
350 kcmil177.3 mm²310 A35.68 V (17.16%)172.3 V58.86 V (28.3%)43264.1 WDrop/Amp High
400 kcmil202.7 mm²335 A31.21 V (15.01%)176.8 V51.49 V (24.75%)37842.7 WDrop/Amp High
500 kcmil253.4 mm²380 A24.97 V (12.0%)183.0 V41.18 V (19.8%)30271.2 WDrop/Amp High
600 kcmil304.0 mm²420 A20.81 V (10.01%)187.2 V34.33 V (16.5%)25232.6 WDrop/Amp High
750 kcmil380.0 mm²475 A16.65 V (8.0%)191.4 V27.46 V (13.2%)20186.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.49 V (6.0%)195.5 V20.6 V (9.9%)15138.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 800 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.25V (3.0%) and delivers 201.8V at the load.

What size aluminum wire is required for 700 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.6V (9.9%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.