⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.96V (6.64%)
Voltage at Load End117.6 VLoss: 2.42 V (1810.2 W)
Power & Breaker (125%)90.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1175.97 V (979.98%)0.0 V1939.8 V (1616.5%)881978.4 WDrop/Amp High
12 AWG3.31 mm²20 A738.98 V (615.82%)0.0 V1218.97 V (1015.81%)554234.1 WDrop/Amp High
10 AWG5.26 mm²30 A465.02 V (387.52%)0.0 V767.07 V (639.23%)348767.1 WDrop/Amp High
8 AWG8.37 mm²50 A292.24 V (243.53%)0.0 V482.05 V (401.71%)219177.4 WDrop/Amp High
6 AWG13.3 mm²65 A183.91 V (153.26%)0.0 V303.37 V (252.81%)137933.5 WDrop/Amp High
4 AWG21.15 mm²85 A115.65 V (96.38%)4.3 V190.77 V (158.98%)86738.3 WDrop/Amp High
3 AWG26.67 mm²100 A91.71 V (76.43%)28.3 V151.29 V (126.07%)68785.7 WDrop/Amp High
2 AWG33.62 mm²115 A72.75 V (60.63%)47.2 V120.01 V (100.01%)54566.2 WDrop/Amp High
1 AWG42.41 mm²130 A57.68 V (48.06%)62.3 V95.14 V (79.28%)43256.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A45.73 V (38.11%)74.3 V75.43 V (62.86%)34296.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A36.27 V (30.23%)83.7 V59.84 V (49.86%)27206.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A28.77 V (23.98%)91.2 V47.46 V (39.55%)21580.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.82 V (19.01%)97.2 V37.64 V (31.36%)17113.0 WDrop/Amp High
250 kcmil126.7 mm²255 A19.31 V (16.09%)100.7 V31.85 V (26.54%)14479.2 WDrop/Amp High
300 kcmil152.0 mm²285 A16.09 V (13.41%)103.9 V26.54 V (22.12%)12069.2 WDrop/Amp High
350 kcmil177.3 mm²310 A13.8 V (11.5%)106.2 V22.76 V (18.96%)10347.0 WDrop/Amp High
400 kcmil202.7 mm²335 A12.07 V (10.06%)107.9 V19.91 V (16.59%)9050.4 WDrop/Amp High
500 kcmil253.4 mm²380 A9.65 V (8.04%)110.3 V15.92 V (13.27%)7239.6 WDrop/Amp High
600 kcmil304.0 mm²420 A8.05 V (6.71%)112.0 V13.27 V (11.06%)6034.6 WDrop/Amp High
750 kcmil380.0 mm²475 A6.44 V (5.36%)113.6 V10.62 V (8.85%)4827.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.83 V (4.02%)115.2 V7.96 V (6.64%)3620.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 250 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.42V (2.01%) and delivers 117.6V at the load.

What size aluminum wire is required for 750 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.96V (6.64%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.