🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.76V (7.3%)
Voltage at Load End117.3 VLoss: 2.65 V (1991.3 W)
Power & Breaker (125%)90.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1293.57 V (1077.97%)0.0 V2133.78 V (1778.15%)970176.2 WDrop/Amp High
12 AWG3.31 mm²20 A812.88 V (677.4%)0.0 V1340.87 V (1117.39%)609657.6 WDrop/Amp High
10 AWG5.26 mm²30 A511.53 V (426.27%)0.0 V843.78 V (703.15%)383643.8 WDrop/Amp High
8 AWG8.37 mm²50 A321.46 V (267.88%)0.0 V530.26 V (441.88%)241095.2 WDrop/Amp High
6 AWG13.3 mm²65 A202.3 V (168.59%)0.0 V333.7 V (278.09%)151726.8 WDrop/Amp High
4 AWG21.15 mm²85 A127.22 V (106.01%)0.0 V209.85 V (174.87%)95412.1 WDrop/Amp High
3 AWG26.67 mm²100 A100.89 V (84.07%)19.1 V166.41 V (138.68%)75664.3 WDrop/Amp High
2 AWG33.62 mm²115 A80.03 V (66.69%)40.0 V132.01 V (110.01%)60022.8 WDrop/Amp High
1 AWG42.41 mm²130 A63.44 V (52.87%)56.6 V104.65 V (87.21%)47582.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A50.3 V (41.92%)69.7 V82.97 V (69.14%)37726.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A39.9 V (33.25%)80.1 V65.82 V (54.85%)29926.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A31.65 V (26.38%)88.3 V52.21 V (43.51%)23738.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.1 V (20.92%)94.9 V41.4 V (34.5%)18824.3 WDrop/Amp High
250 kcmil126.7 mm²255 A21.24 V (17.7%)98.8 V35.03 V (29.19%)15927.1 WDrop/Amp High
300 kcmil152.0 mm²285 A17.7 V (14.75%)102.3 V29.2 V (24.33%)13276.1 WDrop/Amp High
350 kcmil177.3 mm²310 A15.18 V (12.65%)104.8 V25.03 V (20.86%)11381.6 WDrop/Amp High
400 kcmil202.7 mm²335 A13.27 V (11.06%)106.7 V21.9 V (18.25%)9955.4 WDrop/Amp High
500 kcmil253.4 mm²380 A10.62 V (8.85%)109.4 V17.51 V (14.6%)7963.6 WDrop/Amp High
600 kcmil304.0 mm²420 A8.85 V (7.38%)111.1 V14.6 V (12.17%)6638.0 WDrop/Amp High
750 kcmil380.0 mm²475 A7.08 V (5.9%)112.9 V11.68 V (9.73%)5310.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.31 V (4.43%)114.7 V8.76 V (7.3%)3982.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 275 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.65V (2.21%) and delivers 117.3V at the load.

What size aluminum wire is required for 750 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.76V (7.3%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.