⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.15V (4.65%)
Voltage at Load End236.6 VLoss: 3.38 V (2534.3 W)
Power & Breaker (125%)180.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1646.36 V (685.98%)0.0 V2715.72 V (1131.55%)1234769.7 WDrop/Amp High
12 AWG3.31 mm²20 A1034.57 V (431.07%)0.0 V1706.56 V (711.07%)775927.8 WDrop/Amp High
10 AWG5.26 mm²30 A651.03 V (271.26%)0.0 V1073.9 V (447.46%)488274.0 WDrop/Amp High
8 AWG8.37 mm²50 A409.13 V (170.47%)0.0 V674.88 V (281.2%)306848.4 WDrop/Amp High
6 AWG13.3 mm²65 A257.48 V (107.28%)0.0 V424.71 V (176.96%)193106.8 WDrop/Amp High
4 AWG21.15 mm²85 A161.91 V (67.46%)78.1 V267.08 V (111.28%)121433.6 WDrop/Amp High
3 AWG26.67 mm²100 A128.4 V (53.5%)111.6 V211.8 V (88.25%)96300.0 WDrop/Amp High
2 AWG33.62 mm²115 A101.86 V (42.44%)138.1 V168.02 V (70.01%)76392.7 WDrop/Amp High
1 AWG42.41 mm²130 A80.75 V (33.64%)159.3 V133.19 V (55.5%)60559.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A64.02 V (26.67%)176.0 V105.6 V (44.0%)48015.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A50.78 V (21.16%)189.2 V83.77 V (34.9%)38088.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A40.28 V (16.78%)199.7 V66.45 V (27.69%)30212.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.94 V (13.31%)208.1 V52.69 V (21.96%)23958.2 WDrop/Amp High
250 kcmil126.7 mm²255 A27.03 V (11.26%)213.0 V44.58 V (18.58%)20270.9 WDrop/Amp High
300 kcmil152.0 mm²285 A22.53 V (9.39%)217.5 V37.16 V (15.48%)16896.8 WDrop/Amp High
350 kcmil177.3 mm²310 A19.31 V (8.05%)220.7 V31.86 V (13.27%)14485.7 WDrop/Amp High
400 kcmil202.7 mm²335 A16.89 V (7.04%)223.1 V27.87 V (11.61%)12670.6 WDrop/Amp High
500 kcmil253.4 mm²380 A13.51 V (5.63%)226.5 V22.29 V (9.29%)10135.4 WDrop/Amp High
600 kcmil304.0 mm²420 A11.26 V (4.69%)228.7 V18.58 V (7.74%)8448.4 WDrop/Amp High
750 kcmil380.0 mm²475 A9.01 V (3.75%)231.0 V14.87 V (6.19%)6758.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.76 V (2.82%)233.2 V11.15 V (4.65%)5068.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 350 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.38V (1.41%) and delivers 236.6V at the load.

What size aluminum wire is required for 750 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.15V (4.65%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.