🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 600 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.55V (3.45%)
Voltage at Load End475.0 VLoss: 5.01 V (6516.9 W)
Power & Breaker (125%)623.54 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 600 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2444.21 V (509.21%)0.0 V4031.8 V (839.96%)3175122.1 WDrop/Amp High
12 AWG3.31 mm²20 A1535.94 V (319.99%)0.0 V2533.58 V (527.83%)1995242.9 WDrop/Amp High
10 AWG5.26 mm²30 A966.53 V (201.36%)0.0 V1594.33 V (332.15%)1255561.6 WDrop/Amp High
8 AWG8.37 mm²50 A607.4 V (126.54%)0.0 V1001.93 V (208.74%)789038.7 WDrop/Amp High
6 AWG13.3 mm²65 A382.25 V (79.64%)97.7 V630.54 V (131.36%)496560.5 WDrop/Amp High
4 AWG21.15 mm²85 A240.38 V (50.08%)239.6 V396.51 V (82.61%)312257.9 WDrop/Amp High
3 AWG26.67 mm²100 A190.62 V (39.71%)289.4 V314.44 V (65.51%)247628.6 WDrop/Amp High
2 AWG33.62 mm²115 A151.22 V (31.5%)328.8 V249.44 V (51.97%)196438.3 WDrop/Amp High
1 AWG42.41 mm²130 A119.88 V (24.97%)360.1 V197.74 V (41.2%)155724.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A95.05 V (19.8%)385.0 V156.78 V (32.66%)123467.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A75.4 V (15.71%)404.6 V124.37 V (25.91%)97942.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A59.8 V (12.46%)420.2 V98.65 V (20.55%)77688.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A47.42 V (9.88%)432.6 V78.23 V (16.3%)61606.8 WDrop/Amp High
250 kcmil126.7 mm²255 A40.13 V (8.36%)439.9 V66.19 V (13.79%)52125.1 WDrop/Amp High
300 kcmil152.0 mm²285 A33.45 V (6.97%)446.6 V55.17 V (11.49%)43449.0 WDrop/Amp High
350 kcmil177.3 mm²310 A28.67 V (5.97%)451.3 V47.3 V (9.85%)37249.0 WDrop/Amp High
400 kcmil202.7 mm²335 A25.08 V (5.23%)454.9 V41.37 V (8.62%)32581.4 WDrop/Amp High
500 kcmil253.4 mm²380 A20.06 V (4.18%)459.9 V33.09 V (6.89%)26062.6 WDrop/Amp High
600 kcmil304.0 mm²420 A16.72 V (3.48%)463.3 V27.59 V (5.75%)21724.5 WDrop/Amp High
750 kcmil380.0 mm²475 A13.38 V (2.79%)466.6 V22.07 V (4.6%)17379.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.03 V (2.09%)470.0 V16.55 V (3.45%)13033.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 600 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 600 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.01V (1.04%) and delivers 475.0V at the load.

What size aluminum wire is required for 750 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.55V (3.45%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.