🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 120 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.94%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.08V (33.97%)
Voltage at Load End11.7 VLoss: 0.35 V (282.5 W)
Power & Breaker (125%)9.6 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 120 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A602.1 V (5017.48%)0.0 V993.18 V (8276.49%)481677.8 WDrop/Amp High
12 AWG3.31 mm²20 A378.36 V (3152.98%)0.0 V624.11 V (5200.94%)302685.7 WDrop/Amp High
10 AWG5.26 mm²30 A238.09 V (1984.1%)0.0 V392.74 V (3272.83%)190473.3 WDrop/Amp High
8 AWG8.37 mm²50 A149.63 V (1246.88%)0.0 V246.81 V (2056.76%)119700.1 WDrop/Amp High
6 AWG13.3 mm²65 A94.16 V (784.69%)0.0 V155.32 V (1294.37%)75330.1 WDrop/Amp High
4 AWG21.15 mm²85 A59.21 V (493.44%)0.0 V97.67 V (813.95%)47370.7 WDrop/Amp High
3 AWG26.67 mm²100 A46.96 V (391.31%)0.0 V77.46 V (645.49%)37566.2 WDrop/Amp High
2 AWG33.62 mm²115 A37.25 V (310.42%)0.0 V61.45 V (512.05%)29800.4 WDrop/Amp High
1 AWG42.41 mm²130 A29.53 V (246.08%)0.0 V48.71 V (405.92%)23623.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.41 V (195.11%)0.0 V38.62 V (321.84%)18730.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.57 V (154.77%)0.0 V30.64 V (255.3%)14858.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.73 V (122.77%)0.0 V24.3 V (202.51%)11785.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.68 V (97.35%)0.3 V19.27 V (160.59%)9346.0 WDrop/Amp High
250 kcmil126.7 mm²255 A9.88 V (82.37%)2.1 V16.3 V (135.87%)7907.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.24 V (68.66%)3.8 V13.59 V (113.26%)6591.4 WDrop/Amp High
350 kcmil177.3 mm²310 A7.06 V (58.86%)4.9 V11.65 V (97.1%)5650.8 WDrop/Amp High
400 kcmil202.7 mm²335 A6.18 V (51.49%)5.8 V10.19 V (84.93%)4942.7 WDrop/Amp High
500 kcmil253.4 mm²380 A4.94 V (41.19%)7.1 V8.15 V (67.94%)3953.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.12 V (34.33%)7.9 V6.8 V (56.63%)3295.7 WDrop/Amp High
750 kcmil380.0 mm²475 A3.3 V (27.46%)8.7 V5.44 V (45.3%)2636.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.47 V (20.6%)9.5 V4.08 V (33.97%)1977.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 120 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 120 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.94%) and delivers 11.7V at the load.

What size aluminum wire is required for 800 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.08V (33.97%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.