🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.72V (22.65%)
Voltage at Load End11.7 VLoss: 0.33 V (263.6 W)
Power & Breaker (125%)9.6 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A401.4 V (3344.98%)0.0 V662.12 V (5517.66%)321118.5 WDrop/Amp High
12 AWG3.31 mm²20 A252.24 V (2101.98%)0.0 V416.08 V (3467.29%)201790.5 WDrop/Amp High
10 AWG5.26 mm²30 A158.73 V (1322.73%)0.0 V261.83 V (2181.89%)126982.2 WDrop/Amp High
8 AWG8.37 mm²50 A99.75 V (831.25%)0.0 V164.54 V (1371.18%)79800.1 WDrop/Amp High
6 AWG13.3 mm²65 A62.78 V (523.13%)0.0 V103.55 V (862.91%)50220.0 WDrop/Amp High
4 AWG21.15 mm²85 A39.48 V (328.96%)0.0 V65.12 V (542.64%)31580.5 WDrop/Amp High
3 AWG26.67 mm²100 A31.31 V (260.88%)0.0 V51.64 V (430.32%)25044.1 WDrop/Amp High
2 AWG33.62 mm²115 A24.83 V (206.95%)0.0 V40.96 V (341.37%)19866.9 WDrop/Amp High
1 AWG42.41 mm²130 A19.69 V (164.05%)0.0 V32.47 V (270.61%)15749.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.61 V (130.07%)0.0 V25.75 V (214.56%)12486.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.38 V (103.18%)0.0 V20.42 V (170.2%)9905.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.82 V (81.84%)2.2 V16.2 V (135.0%)7857.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.79 V (64.9%)4.2 V12.85 V (107.06%)6230.7 WDrop/Amp High
250 kcmil126.7 mm²255 A6.59 V (54.91%)5.4 V10.87 V (90.58%)5271.7 WDrop/Amp High
300 kcmil152.0 mm²285 A5.49 V (45.77%)6.5 V9.06 V (75.5%)4394.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.71 V (39.24%)7.3 V7.77 V (64.73%)3767.2 WDrop/Amp High
400 kcmil202.7 mm²335 A4.12 V (34.32%)7.9 V6.79 V (56.62%)3295.1 WDrop/Amp High
500 kcmil253.4 mm²380 A3.29 V (27.46%)8.7 V5.43 V (45.29%)2635.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.75 V (22.89%)9.3 V4.53 V (37.75%)2197.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.2 V (18.31%)9.8 V3.62 V (30.2%)1757.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.65 V (13.73%)10.4 V2.72 V (22.65%)1318.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 80 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.75%) and delivers 11.7V at the load.

What size aluminum wire is required for 800 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.72V (22.65%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.