⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 25.48V (10.62%)
Voltage at Load End234.8 VLoss: 5.15 V (4119.3 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3763.11 V (1567.96%)0.0 V6207.37 V (2586.4%)3010486.2 WDrop/Amp High
12 AWG3.31 mm²20 A2364.73 V (985.31%)0.0 V3900.7 V (1625.29%)1891785.9 WDrop/Amp High
10 AWG5.26 mm²30 A1488.07 V (620.03%)0.0 V2454.63 V (1022.76%)1190458.4 WDrop/Amp High
8 AWG8.37 mm²50 A935.16 V (389.65%)0.0 V1542.57 V (642.74%)748125.6 WDrop/Amp High
6 AWG13.3 mm²65 A588.52 V (245.22%)0.0 V970.78 V (404.49%)470812.9 WDrop/Amp High
4 AWG21.15 mm²85 A370.08 V (154.2%)0.0 V610.46 V (254.36%)296066.7 WDrop/Amp High
3 AWG26.67 mm²100 A293.49 V (122.29%)0.0 V484.11 V (201.71%)234788.6 WDrop/Amp High
2 AWG33.62 mm²115 A232.82 V (97.01%)7.2 V384.04 V (160.02%)186252.6 WDrop/Amp High
1 AWG42.41 mm²130 A184.56 V (76.9%)55.4 V304.44 V (126.85%)147649.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A146.33 V (60.97%)93.7 V241.38 V (100.57%)117065.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A116.08 V (48.37%)123.9 V191.48 V (79.78%)92863.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A92.07 V (38.36%)147.9 V151.88 V (63.28%)73659.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A73.02 V (30.42%)167.0 V120.44 V (50.18%)58412.4 WDrop/Amp High
250 kcmil126.7 mm²255 A61.78 V (25.74%)178.2 V101.9 V (42.46%)49422.3 WDrop/Amp High
300 kcmil152.0 mm²285 A51.5 V (21.46%)188.5 V84.94 V (35.39%)41196.1 WDrop/Amp High
350 kcmil177.3 mm²310 A44.15 V (18.39%)195.9 V72.82 V (30.34%)35317.6 WDrop/Amp High
400 kcmil202.7 mm²335 A38.62 V (16.09%)201.4 V63.7 V (26.54%)30892.0 WDrop/Amp High
500 kcmil253.4 mm²380 A30.89 V (12.87%)209.1 V50.95 V (21.23%)24711.2 WDrop/Amp High
600 kcmil304.0 mm²420 A25.75 V (10.73%)214.3 V42.47 V (17.7%)20598.1 WDrop/Amp High
750 kcmil380.0 mm²475 A20.6 V (8.58%)219.4 V33.98 V (14.16%)16478.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A15.45 V (6.44%)224.6 V25.48 V (10.62%)12358.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 750 feet one-way at 240V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.15V (2.15%) and delivers 234.8V at the load.

What size aluminum wire is required for 800 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 25.48V (10.62%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.