🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 0.64%
Aluminum Wire (≤3% Drop)2 AWGDrop: 3.99V (0.83%)
Voltage at Load End477.0 VLoss: 3.05 V (475.4 W)
Power & Breaker (125%)74.82 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A39.11 V (8.15%)440.9 V64.51 V (13.44%)6096.2 WDrop/Amp High
12 AWG3.31 mm²20 A24.58 V (5.12%)455.4 V40.54 V (8.45%)3830.9 WDrop/Amp High
10 AWG5.26 mm²30 A15.46 V (3.22%)464.5 V25.51 V (5.31%)2410.7 WDrop/Amp High
8 AWG8.37 mm²50 A9.72 V (2.02%)470.3 V16.03 V (3.34%)1515.0 WDrop/Amp High
6 AWG13.3 mm²65 A6.12 V (1.27%)473.9 V10.09 V (2.1%)953.4 WDrop/Amp High
4 AWG21.15 mm²85 A3.85 V (0.8%)476.2 V6.34 V (1.32%)599.5 WDrop/Amp High
3 AWG26.67 mm²100 A3.05 V (0.64%)477.0 V5.03 V (1.05%)475.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.42 V (0.5%)477.6 V3.99 V (0.83%)377.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.92 V (0.4%)478.1 V3.16 V (0.66%)299.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.52 V (0.32%)478.5 V2.51 V (0.52%)237.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.21 V (0.25%)478.8 V1.99 V (0.41%)188.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.96 V (0.2%)479.0 V1.58 V (0.33%)149.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.76 V (0.16%)479.2 V1.25 V (0.26%)118.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.64 V (0.13%)479.4 V1.06 V (0.22%)100.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.54 V (0.11%)479.5 V0.88 V (0.18%)83.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.46 V (0.1%)479.5 V0.76 V (0.16%)71.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.4 V (0.08%)479.6 V0.66 V (0.14%)62.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.32 V (0.07%)479.7 V0.53 V (0.11%)50.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.27 V (0.06%)479.7 V0.44 V (0.09%)41.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.21 V (0.04%)479.8 V0.35 V (0.07%)33.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.16 V (0.03%)479.8 V0.26 V (0.06%)25.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 80 feet one-way at 480V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 3.05V (0.64%) and delivers 477.0V at the load.

What size aluminum wire is required for 90 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 3.99V (0.83%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.