⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 0.99%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.24V (1.3%)
Voltage at Load End475.2 VLoss: 4.77 V (742.9 W)
Power & Breaker (125%)74.82 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A61.11 V (12.73%)418.9 V100.8 V (21.0%)9525.4 WDrop/Amp High
12 AWG3.31 mm²20 A38.4 V (8.0%)441.6 V63.34 V (13.2%)5985.7 WDrop/Amp High
10 AWG5.26 mm²30 A24.16 V (5.03%)455.8 V39.86 V (8.3%)3766.7 WDrop/Amp High
8 AWG8.37 mm²50 A15.19 V (3.16%)464.8 V25.05 V (5.22%)2367.1 WDrop/Amp High
6 AWG13.3 mm²65 A9.56 V (1.99%)470.4 V15.76 V (3.28%)1489.7 WDrop/Amp High
4 AWG21.15 mm²85 A6.01 V (1.25%)474.0 V9.91 V (2.07%)936.8 WDrop/Amp High
3 AWG26.67 mm²100 A4.77 V (0.99%)475.2 V7.86 V (1.64%)742.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.78 V (0.79%)476.2 V6.24 V (1.3%)589.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.0 V (0.62%)477.0 V4.94 V (1.03%)467.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.38 V (0.5%)477.6 V3.92 V (0.82%)370.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.88 V (0.39%)478.1 V3.11 V (0.65%)293.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.5 V (0.31%)478.5 V2.47 V (0.51%)233.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.19 V (0.25%)478.8 V1.96 V (0.41%)184.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.0 V (0.21%)479.0 V1.65 V (0.34%)156.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.84 V (0.17%)479.2 V1.38 V (0.29%)130.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.72 V (0.15%)479.3 V1.18 V (0.25%)111.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.63 V (0.13%)479.4 V1.03 V (0.22%)97.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.5 V (0.1%)479.5 V0.83 V (0.17%)78.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.42 V (0.09%)479.6 V0.69 V (0.14%)65.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.07%)479.7 V0.55 V (0.11%)52.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.05%)479.7 V0.41 V (0.09%)39.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 125 feet one-way at 480V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 4.77V (0.99%) and delivers 475.2V at the load.

What size aluminum wire is required for 90 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.24V (1.3%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.