🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 800 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.06V (25.48%)
Voltage at Load End11.7 VLoss: 0.31 V (27.8 W)
Power & Breaker (125%)1.08 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 800 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A451.57 V (3763.11%)0.0 V744.88 V (6207.37%)40641.6 WDrop/Amp High
12 AWG3.31 mm²20 A283.77 V (2364.73%)0.0 V468.08 V (3900.7%)25539.1 WDrop/Amp High
10 AWG5.26 mm²30 A178.57 V (1488.07%)0.0 V294.56 V (2454.63%)16071.2 WDrop/Amp High
8 AWG8.37 mm²50 A112.22 V (935.16%)0.0 V185.11 V (1542.57%)10099.7 WDrop/Amp High
6 AWG13.3 mm²65 A70.62 V (588.52%)0.0 V116.49 V (970.78%)6356.0 WDrop/Amp High
4 AWG21.15 mm²85 A44.41 V (370.08%)0.0 V73.26 V (610.46%)3996.9 WDrop/Amp High
3 AWG26.67 mm²100 A35.22 V (293.49%)0.0 V58.09 V (484.11%)3169.6 WDrop/Amp High
2 AWG33.62 mm²115 A27.94 V (232.82%)0.0 V46.08 V (384.04%)2514.4 WDrop/Amp High
1 AWG42.41 mm²130 A22.15 V (184.56%)0.0 V36.53 V (304.44%)1993.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.56 V (146.33%)0.0 V28.97 V (241.38%)1580.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.93 V (116.08%)0.0 V22.98 V (191.48%)1253.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.05 V (92.07%)1.0 V18.23 V (151.88%)994.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.76 V (73.02%)3.2 V14.45 V (120.44%)788.6 WDrop/Amp High
250 kcmil126.7 mm²255 A7.41 V (61.78%)4.6 V12.23 V (101.9%)667.2 WDrop/Amp High
300 kcmil152.0 mm²285 A6.18 V (51.5%)5.8 V10.19 V (84.94%)556.1 WDrop/Amp High
350 kcmil177.3 mm²310 A5.3 V (44.15%)6.7 V8.74 V (72.82%)476.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.63 V (38.62%)7.4 V7.64 V (63.7%)417.0 WDrop/Amp High
500 kcmil253.4 mm²380 A3.71 V (30.89%)8.3 V6.11 V (50.95%)333.6 WDrop/Amp High
600 kcmil304.0 mm²420 A3.09 V (25.75%)8.9 V5.1 V (42.47%)278.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.47 V (20.6%)9.5 V4.08 V (33.98%)222.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.85 V (15.45%)10.1 V3.06 V (25.48%)166.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 800 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 800 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (2.57%) and delivers 11.7V at the load.

What size aluminum wire is required for 90 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.06V (25.48%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.