🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 1000 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 38.22V (31.85%)
Voltage at Load End116.7 VLoss: 3.31 V (2979.2 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 1000 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5644.66 V (4703.88%)0.0 V9311.05 V (7759.21%)5080195.4 WDrop/Amp High
12 AWG3.31 mm²20 A3547.1 V (2955.92%)0.0 V5851.05 V (4875.88%)3192388.6 WDrop/Amp High
10 AWG5.26 mm²30 A2232.11 V (1860.09%)0.0 V3681.94 V (3068.28%)2008898.6 WDrop/Amp High
8 AWG8.37 mm²50 A1402.74 V (1168.95%)0.0 V2313.86 V (1928.22%)1262461.9 WDrop/Amp High
6 AWG13.3 mm²65 A882.77 V (735.65%)0.0 V1456.16 V (1213.47%)794496.7 WDrop/Amp High
4 AWG21.15 mm²85 A555.13 V (462.6%)0.0 V915.7 V (763.08%)499612.6 WDrop/Amp High
3 AWG26.67 mm²100 A440.23 V (366.86%)0.0 V726.17 V (605.14%)396205.7 WDrop/Amp High
2 AWG33.62 mm²115 A349.22 V (291.02%)0.0 V576.06 V (480.05%)314301.2 WDrop/Amp High
1 AWG42.41 mm²130 A276.84 V (230.7%)0.0 V456.66 V (380.55%)249158.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A219.5 V (182.91%)0.0 V362.07 V (301.72%)197547.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A174.12 V (145.1%)0.0 V287.22 V (239.35%)156707.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A138.11 V (115.09%)0.0 V227.82 V (189.85%)124300.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A109.52 V (91.27%)10.5 V180.66 V (150.55%)98571.0 WDrop/Amp High
250 kcmil126.7 mm²255 A92.67 V (77.22%)27.3 V152.86 V (127.38%)83400.2 WDrop/Amp High
300 kcmil152.0 mm²285 A77.24 V (64.37%)42.8 V127.41 V (106.18%)69518.5 WDrop/Amp High
350 kcmil177.3 mm²310 A66.22 V (55.18%)53.8 V109.23 V (91.03%)59598.5 WDrop/Amp High
400 kcmil202.7 mm²335 A57.92 V (48.27%)62.1 V95.55 V (79.62%)52130.3 WDrop/Amp High
500 kcmil253.4 mm²380 A46.33 V (38.61%)73.7 V76.43 V (63.69%)41700.1 WDrop/Amp High
600 kcmil304.0 mm²420 A38.62 V (32.18%)81.4 V63.71 V (53.09%)34759.2 WDrop/Amp High
750 kcmil380.0 mm²475 A30.9 V (25.75%)89.1 V50.97 V (42.47%)27807.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A23.17 V (19.31%)96.8 V38.22 V (31.85%)20854.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 1000 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 1000 feet one-way at 120V (1-Phase), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.31V (2.76%) and delivers 116.7V at the load.

What size aluminum wire is required for 900 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 38.22V (31.85%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.