⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 38.22V (15.93%)
Voltage at Load End234.2 VLoss: 5.79 V (5213.6 W)
Power & Breaker (125%)216.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5644.66 V (2351.94%)0.0 V9311.05 V (3879.61%)5080195.4 WDrop/Amp High
12 AWG3.31 mm²20 A3547.1 V (1477.96%)0.0 V5851.05 V (2437.94%)3192388.6 WDrop/Amp High
10 AWG5.26 mm²30 A2232.11 V (930.05%)0.0 V3681.94 V (1534.14%)2008898.6 WDrop/Amp High
8 AWG8.37 mm²50 A1402.74 V (584.47%)0.0 V2313.86 V (964.11%)1262461.9 WDrop/Amp High
6 AWG13.3 mm²65 A882.77 V (367.82%)0.0 V1456.16 V (606.74%)794496.7 WDrop/Amp High
4 AWG21.15 mm²85 A555.13 V (231.3%)0.0 V915.7 V (381.54%)499612.6 WDrop/Amp High
3 AWG26.67 mm²100 A440.23 V (183.43%)0.0 V726.17 V (302.57%)396205.7 WDrop/Amp High
2 AWG33.62 mm²115 A349.22 V (145.51%)0.0 V576.06 V (240.02%)314301.2 WDrop/Amp High
1 AWG42.41 mm²130 A276.84 V (115.35%)0.0 V456.66 V (190.28%)249158.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A219.5 V (91.46%)20.5 V362.07 V (150.86%)197547.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A174.12 V (72.55%)65.9 V287.22 V (119.67%)156707.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A138.11 V (57.55%)101.9 V227.82 V (94.93%)124300.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A109.52 V (45.63%)130.5 V180.66 V (75.28%)98571.0 WDrop/Amp High
250 kcmil126.7 mm²255 A92.67 V (38.61%)147.3 V152.86 V (63.69%)83400.2 WDrop/Amp High
300 kcmil152.0 mm²285 A77.24 V (32.18%)162.8 V127.41 V (53.09%)69518.5 WDrop/Amp High
350 kcmil177.3 mm²310 A66.22 V (27.59%)173.8 V109.23 V (45.51%)59598.5 WDrop/Amp High
400 kcmil202.7 mm²335 A57.92 V (24.13%)182.1 V95.55 V (39.81%)52130.3 WDrop/Amp High
500 kcmil253.4 mm²380 A46.33 V (19.31%)193.7 V76.43 V (31.85%)41700.1 WDrop/Amp High
600 kcmil304.0 mm²420 A38.62 V (16.09%)201.4 V63.71 V (26.54%)34759.2 WDrop/Amp High
750 kcmil380.0 mm²475 A30.9 V (12.87%)209.1 V50.97 V (21.24%)27807.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A23.17 V (9.65%)216.8 V38.22 V (15.93%)20854.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 1000 feet one-way at 240V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.79V (2.41%) and delivers 234.2V at the load.

What size aluminum wire is required for 900 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 38.22V (15.93%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.