🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 300 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.93V (4.14%)
Voltage at Load End237.0 VLoss: 3.01 V (4692.2 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 300 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1466.53 V (611.05%)0.0 V2419.08 V (1007.95%)2286087.9 WDrop/Amp High
12 AWG3.31 mm²20 A921.56 V (383.98%)0.0 V1520.15 V (633.4%)1436574.9 WDrop/Amp High
10 AWG5.26 mm²30 A579.92 V (241.63%)0.0 V956.6 V (398.58%)904004.3 WDrop/Amp High
8 AWG8.37 mm²50 A364.44 V (151.85%)0.0 V601.16 V (250.48%)568107.9 WDrop/Amp High
6 AWG13.3 mm²65 A229.35 V (95.56%)10.6 V378.32 V (157.63%)357523.5 WDrop/Amp High
4 AWG21.15 mm²85 A144.23 V (60.09%)95.8 V237.91 V (99.13%)224825.7 WDrop/Amp High
3 AWG26.67 mm²100 A114.37 V (47.66%)125.6 V188.66 V (78.61%)178292.6 WDrop/Amp High
2 AWG33.62 mm²115 A90.73 V (37.8%)149.3 V149.66 V (62.36%)141435.5 WDrop/Amp High
1 AWG42.41 mm²130 A71.93 V (29.97%)168.1 V118.64 V (49.44%)112121.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A57.03 V (23.76%)183.0 V94.07 V (39.19%)88896.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A45.24 V (18.85%)194.8 V74.62 V (31.09%)70518.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A35.88 V (14.95%)204.1 V59.19 V (24.66%)55935.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A28.45 V (11.86%)211.5 V46.94 V (19.56%)44356.9 WDrop/Amp High
250 kcmil126.7 mm²255 A24.08 V (10.03%)215.9 V39.71 V (16.55%)37530.1 WDrop/Amp High
300 kcmil152.0 mm²285 A20.07 V (8.36%)219.9 V33.1 V (13.79%)31283.3 WDrop/Amp High
350 kcmil177.3 mm²310 A17.2 V (7.17%)222.8 V28.38 V (11.82%)26819.3 WDrop/Amp High
400 kcmil202.7 mm²335 A15.05 V (6.27%)225.0 V24.82 V (10.34%)23458.6 WDrop/Amp High
500 kcmil253.4 mm²380 A12.04 V (5.02%)228.0 V19.86 V (8.27%)18765.0 WDrop/Amp High
600 kcmil304.0 mm²420 A10.03 V (4.18%)230.0 V16.55 V (6.9%)15641.7 WDrop/Amp High
750 kcmil380.0 mm²475 A8.03 V (3.34%)232.0 V13.24 V (5.52%)12513.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.02 V (2.51%)234.0 V9.93 V (4.14%)9384.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 300 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 300 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.01V (1.25%) and delivers 237.0V at the load.

What size aluminum wire is required for 900 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.93V (4.14%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.