10 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 13.34V (1.93%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 13.76V (1.99%)
Voltage at Load676.7 VLine Loss: 231.1 W
Max Power & Breaker11.95 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.24 V (3.22%)667.8 V36.68 V (5.32%)385.2 W~ ≤5%
2.5 mm²24 A18 A13.34 V (1.93%)676.7 V22.01 V (3.19%)231.1 W✓ OK (≤3%)
4 mm²32 A25 A8.34 V (1.21%)681.7 V13.76 V (1.99%)144.4 W✓ OK (≤3%)
6 mm²41 A32 A5.56 V (0.81%)684.4 V9.17 V (1.33%)96.3 W✓ OK (≤3%)
10 mm²57 A44 A3.34 V (0.48%)686.7 V5.5 V (0.8%)57.8 W✓ OK (≤3%)
16 mm²76 A59 A2.08 V (0.3%)687.9 V3.44 V (0.5%)36.1 W✓ OK (≤3%)
25 mm²101 A78 A1.33 V (0.19%)688.7 V2.2 V (0.32%)23.1 W✓ OK (≤3%)
35 mm²125 A97 A0.95 V (0.14%)689.0 V1.57 V (0.23%)16.5 W✓ OK (≤3%)
50 mm²151 A118 A0.67 V (0.1%)689.3 V1.1 V (0.16%)11.6 W✓ OK (≤3%)
70 mm²192 A150 A0.48 V (0.07%)689.5 V0.79 V (0.11%)8.3 W✓ OK (≤3%)
95 mm²232 A181 A0.35 V (0.05%)689.6 V0.58 V (0.08%)6.1 W✓ OK (≤3%)
120 mm²269 A210 A0.28 V (0.04%)689.7 V0.46 V (0.07%)4.8 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.03%)689.8 V0.37 V (0.05%)3.9 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.03%)689.8 V0.3 V (0.04%)3.1 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.02%)689.9 V0.23 V (0.03%)2.4 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.02%)689.9 V0.18 V (0.03%)1.9 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.01%)689.9 V0.14 V (0.02%)1.4 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 10A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 10A over 90m at 690V (voltage drop: 13.34V or 1.93%).

What is the power capacity of 10A at 690V?

At unity power factor, 10A at 690V supports 11.95 kW with a standard 10A circuit breaker.