40 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 13.34V (1.93%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 13.76V (1.99%)
Voltage at Load676.7 VLine Loss: 924.5 W
Max Power & Breaker47.8 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A88.96 V (12.89%)601.0 V146.74 V (21.27%)6163.2 WDrop High
2.5 mm²24 A18 A53.37 V (7.74%)636.6 V88.04 V (12.76%)3697.9 WDrop High
4 mm²32 A25 A33.36 V (4.83%)656.6 V55.03 V (7.97%)2311.2 WDrop High
6 mm²41 A32 A22.24 V (3.22%)667.8 V36.68 V (5.32%)1540.8 W~ ≤5%
10 mm²57 A44 A13.34 V (1.93%)676.7 V22.01 V (3.19%)924.5 W✓ OK (≤3%)
16 mm²76 A59 A8.34 V (1.21%)681.7 V13.76 V (1.99%)577.8 W✓ OK (≤3%)
25 mm²101 A78 A5.34 V (0.77%)684.7 V8.8 V (1.28%)369.8 W✓ OK (≤3%)
35 mm²125 A97 A3.81 V (0.55%)686.2 V6.29 V (0.91%)264.1 W✓ OK (≤3%)
50 mm²151 A118 A2.67 V (0.39%)687.3 V4.4 V (0.64%)184.9 W✓ OK (≤3%)
70 mm²192 A150 A1.91 V (0.28%)688.1 V3.14 V (0.46%)132.1 W✓ OK (≤3%)
95 mm²232 A181 A1.4 V (0.2%)688.6 V2.32 V (0.34%)97.3 W✓ OK (≤3%)
120 mm²269 A210 A1.11 V (0.16%)688.9 V1.83 V (0.27%)77.0 W✓ OK (≤3%)
150 mm²309 A241 A0.89 V (0.13%)689.1 V1.47 V (0.21%)61.6 W✓ OK (≤3%)
185 mm²353 A275 A0.72 V (0.1%)689.3 V1.19 V (0.17%)50.0 W✓ OK (≤3%)
240 mm²415 A324 A0.56 V (0.08%)689.4 V0.92 V (0.13%)38.5 W✓ OK (≤3%)
300 mm²477 A372 A0.44 V (0.06%)689.6 V0.73 V (0.11%)30.8 W✓ OK (≤3%)
400 mm²570 A445 A0.33 V (0.05%)689.7 V0.55 V (0.08%)23.1 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 40A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 40A over 90m at 690V (voltage drop: 13.34V or 1.93%).

What is the power capacity of 40A at 690V?

At unity power factor, 40A at 690V supports 47.8 kW with a standard 40A circuit breaker.