32 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 17.79V (2.58%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 17.61V (2.55%)
Voltage at Load672.2 VLine Loss: 986.1 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A71.17 V (10.31%)618.8 V117.39 V (17.01%)3944.4 WDrop High
2.5 mm²24 A18 A42.7 V (6.19%)647.3 V70.43 V (10.21%)2366.7 WDrop High
4 mm²32 A25 A26.69 V (3.87%)663.3 V44.02 V (6.38%)1479.2 W~ ≤5%
6 mm²41 A32 A17.79 V (2.58%)672.2 V29.35 V (4.25%)986.1 W✓ OK (≤3%)
10 mm²57 A44 A10.67 V (1.55%)679.3 V17.61 V (2.55%)591.7 W✓ OK (≤3%)
16 mm²76 A59 A6.67 V (0.97%)683.3 V11.01 V (1.59%)369.8 W✓ OK (≤3%)
25 mm²101 A78 A4.27 V (0.62%)685.7 V7.04 V (1.02%)236.7 W✓ OK (≤3%)
35 mm²125 A97 A3.05 V (0.44%)687.0 V5.03 V (0.73%)169.0 W✓ OK (≤3%)
50 mm²151 A118 A2.13 V (0.31%)687.9 V3.52 V (0.51%)118.3 W✓ OK (≤3%)
70 mm²192 A150 A1.52 V (0.22%)688.5 V2.52 V (0.36%)84.5 W✓ OK (≤3%)
95 mm²232 A181 A1.12 V (0.16%)688.9 V1.85 V (0.27%)62.3 W✓ OK (≤3%)
120 mm²269 A210 A0.89 V (0.13%)689.1 V1.47 V (0.21%)49.3 W✓ OK (≤3%)
150 mm²309 A241 A0.71 V (0.1%)689.3 V1.17 V (0.17%)39.4 W✓ OK (≤3%)
185 mm²353 A275 A0.58 V (0.08%)689.4 V0.95 V (0.14%)32.0 W✓ OK (≤3%)
240 mm²415 A324 A0.44 V (0.06%)689.6 V0.73 V (0.11%)24.7 W✓ OK (≤3%)
300 mm²477 A372 A0.36 V (0.05%)689.6 V0.59 V (0.09%)19.7 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.04%)689.7 V0.44 V (0.06%)14.8 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 32A over 90m at 690V (voltage drop: 17.79V or 2.58%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.