⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

80 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 10.67V (1.55%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 12.58V (1.82%)
Voltage at Load679.3 VLine Loss: 1479.2 W
Max Power & Breaker95.61 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A177.92 V (25.78%)512.1 V293.48 V (42.53%)24652.8 WDrop High
2.5 mm²24 A18 A106.75 V (15.47%)583.3 V176.09 V (25.52%)14791.7 WDrop High
4 mm²32 A25 A66.72 V (9.67%)623.3 V110.05 V (15.95%)9244.8 WDrop High
6 mm²41 A32 A44.48 V (6.45%)645.5 V73.37 V (10.63%)6163.2 WDrop High
10 mm²57 A44 A26.69 V (3.87%)663.3 V44.02 V (6.38%)3697.9 WDrop High
16 mm²76 A59 A16.68 V (2.42%)673.3 V27.51 V (3.99%)2311.2 WDrop High
25 mm²101 A78 A10.67 V (1.55%)679.3 V17.61 V (2.55%)1479.2 W✓ OK (≤3%)
35 mm²125 A97 A7.62 V (1.11%)682.4 V12.58 V (1.82%)1056.5 W✓ OK (≤3%)
50 mm²151 A118 A5.34 V (0.77%)684.7 V8.8 V (1.28%)739.6 W✓ OK (≤3%)
70 mm²192 A150 A3.81 V (0.55%)686.2 V6.29 V (0.91%)528.3 W✓ OK (≤3%)
95 mm²232 A181 A2.81 V (0.41%)687.2 V4.63 V (0.67%)389.3 W✓ OK (≤3%)
120 mm²269 A210 A2.22 V (0.32%)687.8 V3.67 V (0.53%)308.2 W✓ OK (≤3%)
150 mm²309 A241 A1.78 V (0.26%)688.2 V2.93 V (0.43%)246.5 W✓ OK (≤3%)
185 mm²353 A275 A1.44 V (0.21%)688.6 V2.38 V (0.34%)199.9 W✓ OK (≤3%)
240 mm²415 A324 A1.11 V (0.16%)688.9 V1.83 V (0.27%)154.1 W✓ OK (≤3%)
300 mm²477 A372 A0.89 V (0.13%)689.1 V1.47 V (0.21%)123.3 W✓ OK (≤3%)
400 mm²570 A445 A0.67 V (0.1%)689.3 V1.1 V (0.16%)92.4 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 80A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 90m at 690V (voltage drop: 10.67V or 1.55%).

What is the power capacity of 80A at 690V?

At unity power factor, 80A at 690V supports 95.61 kW with a standard 80A circuit breaker.