100 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 13.34V (1.93%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.01V (1.59%)
Voltage at Load676.7 VLine Loss: 2311.2 W
Max Power & Breaker119.51 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (32.23%)467.6 V366.85 V (53.17%)38520.0 WDrop High
2.5 mm²24 A18 A133.44 V (19.34%)556.6 V220.11 V (31.9%)23112.0 WDrop High
4 mm²32 A25 A83.4 V (12.09%)606.6 V137.57 V (19.94%)14445.0 WDrop High
6 mm²41 A32 A55.6 V (8.06%)634.4 V91.71 V (13.29%)9630.0 WDrop High
10 mm²57 A44 A33.36 V (4.83%)656.6 V55.03 V (7.97%)5778.0 WDrop High
16 mm²76 A59 A20.85 V (3.02%)669.2 V34.39 V (4.98%)3611.2 WDrop High
25 mm²101 A78 A13.34 V (1.93%)676.7 V22.01 V (3.19%)2311.2 W✓ OK (≤3%)
35 mm²125 A97 A9.53 V (1.38%)680.5 V15.72 V (2.28%)1650.9 W✓ OK (≤3%)
50 mm²151 A118 A6.67 V (0.97%)683.3 V11.01 V (1.59%)1155.6 W✓ OK (≤3%)
70 mm²192 A150 A4.77 V (0.69%)685.2 V7.86 V (1.14%)825.4 W✓ OK (≤3%)
95 mm²232 A181 A3.51 V (0.51%)686.5 V5.79 V (0.84%)608.2 W✓ OK (≤3%)
120 mm²269 A210 A2.78 V (0.4%)687.2 V4.59 V (0.66%)481.5 W✓ OK (≤3%)
150 mm²309 A241 A2.22 V (0.32%)687.8 V3.67 V (0.53%)385.2 W✓ OK (≤3%)
185 mm²353 A275 A1.8 V (0.26%)688.2 V2.97 V (0.43%)312.3 W✓ OK (≤3%)
240 mm²415 A324 A1.39 V (0.2%)688.6 V2.29 V (0.33%)240.7 W✓ OK (≤3%)
300 mm²477 A372 A1.11 V (0.16%)688.9 V1.83 V (0.27%)192.6 W✓ OK (≤3%)
400 mm²570 A445 A0.83 V (0.12%)689.2 V1.38 V (0.2%)144.4 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 100A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 100A over 90m at 690V (voltage drop: 13.34V or 1.93%).

What is the power capacity of 100A at 690V?

At unity power factor, 100A at 690V supports 119.51 kW with a standard 100A circuit breaker.