1000 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 10.81V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 53.5V (12.89%)
Voltage at Load404.2 VLine Loss: 18725.0 W
Max Power & Breaker718.8 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8648.71 V (2084.03%)0.0 V14266.33 V (3437.67%)14980000.0 WDrop High
2.5 mm²24 A18 A5189.22 V (1250.42%)0.0 V8559.8 V (2062.6%)8988000.0 WDrop High
4 mm²32 A25 A3243.27 V (781.51%)0.0 V5349.87 V (1289.13%)5617500.0 WDrop High
6 mm²41 A32 A2162.18 V (521.01%)0.0 V3566.58 V (859.42%)3745000.0 WDrop High
10 mm²57 A44 A1297.31 V (312.6%)0.0 V2139.95 V (515.65%)2247000.0 WDrop High
16 mm²76 A59 A810.82 V (195.38%)0.0 V1337.47 V (322.28%)1404375.0 WDrop High
25 mm²101 A78 A518.92 V (125.04%)0.0 V855.98 V (206.26%)898800.0 WDrop High
35 mm²125 A97 A370.66 V (89.32%)44.3 V611.41 V (147.33%)642000.0 WDrop High
50 mm²151 A118 A259.46 V (62.52%)155.5 V427.99 V (103.13%)449400.0 WDrop High
70 mm²192 A150 A185.33 V (44.66%)229.7 V305.71 V (73.66%)321000.0 WDrop High
95 mm²232 A181 A136.56 V (32.91%)278.4 V225.26 V (54.28%)236526.3 WDrop High
120 mm²269 A210 A108.11 V (26.05%)306.9 V178.33 V (42.97%)187250.0 WDrop High
150 mm²309 A241 A86.49 V (20.84%)328.5 V142.66 V (34.38%)149800.0 WDrop High
185 mm²353 A275 A70.12 V (16.9%)344.9 V115.67 V (27.87%)121459.5 WDrop High
240 mm²415 A324 A54.05 V (13.03%)360.9 V89.16 V (21.49%)93625.0 WDrop High
300 mm²477 A372 A43.24 V (10.42%)371.8 V71.33 V (17.19%)74900.0 WDrop High
400 mm²570 A445 A32.43 V (7.82%)382.6 V53.5 V (12.89%)56175.0 WDrop High

FAQ — 1000 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 1000A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 1000A over 350m at 415V (voltage drop: 10.81V or 2.61%).

What is the power capacity of 1000A at 415V?

At unity power factor, 1000A at 415V supports 718.8 kW with a standard 1000A circuit breaker.