⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

1000 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 18.53V (2.69%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 91.71V (13.29%)
Voltage at Load671.5 VLine Loss: 32100.0 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14826.35 V (2148.75%)0.0 V24456.56 V (3544.43%)25680000.0 WDrop High
2.5 mm²24 A18 A8895.81 V (1289.25%)0.0 V14673.93 V (2126.66%)15408000.0 WDrop High
4 mm²32 A25 A5559.88 V (805.78%)0.0 V9171.21 V (1329.16%)9630000.0 WDrop High
6 mm²41 A32 A3706.59 V (537.19%)0.0 V6114.14 V (886.11%)6420000.0 WDrop High
10 mm²57 A44 A2223.95 V (322.31%)0.0 V3668.48 V (531.66%)3852000.0 WDrop High
16 mm²76 A59 A1389.97 V (201.45%)0.0 V2292.8 V (332.29%)2407500.0 WDrop High
25 mm²101 A78 A889.58 V (128.92%)0.0 V1467.39 V (212.67%)1540800.0 WDrop High
35 mm²125 A97 A635.42 V (92.09%)54.6 V1048.14 V (151.9%)1100571.4 WDrop High
50 mm²151 A118 A444.79 V (64.46%)245.2 V733.7 V (106.33%)770400.0 WDrop High
70 mm²192 A150 A317.71 V (46.04%)372.3 V524.07 V (75.95%)550285.7 WDrop High
95 mm²232 A181 A234.1 V (33.93%)455.9 V386.16 V (55.96%)405473.7 WDrop High
120 mm²269 A210 A185.33 V (26.86%)504.7 V305.71 V (44.31%)321000.0 WDrop High
150 mm²309 A241 A148.26 V (21.49%)541.7 V244.57 V (35.44%)256800.0 WDrop High
185 mm²353 A275 A120.21 V (17.42%)569.8 V198.3 V (28.74%)208216.2 WDrop High
240 mm²415 A324 A92.66 V (13.43%)597.3 V152.85 V (22.15%)160500.0 WDrop High
300 mm²477 A372 A74.13 V (10.74%)615.9 V122.28 V (17.72%)128400.0 WDrop High
400 mm²570 A445 A55.6 V (8.06%)634.4 V91.71 V (13.29%)96300.0 WDrop High

FAQ — 1000 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 1000A over 600m at 690V (voltage drop: 18.53V or 2.69%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.