15 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 13.9V (2.01%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 13.76V (1.99%)
Voltage at Load676.1 VLine Loss: 361.1 W
Max Power & Breaker17.93 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (8.06%)634.4 V91.71 V (13.29%)1444.5 WDrop High
2.5 mm²24 A18 A33.36 V (4.83%)656.6 V55.03 V (7.97%)866.7 W~ ≤5%
4 mm²32 A25 A20.85 V (3.02%)669.2 V34.39 V (4.98%)541.7 W~ ≤5%
6 mm²41 A32 A13.9 V (2.01%)676.1 V22.93 V (3.32%)361.1 W✓ OK (≤3%)
10 mm²57 A44 A8.34 V (1.21%)681.7 V13.76 V (1.99%)216.7 W✓ OK (≤3%)
16 mm²76 A59 A5.21 V (0.76%)684.8 V8.6 V (1.25%)135.4 W✓ OK (≤3%)
25 mm²101 A78 A3.34 V (0.48%)686.7 V5.5 V (0.8%)86.7 W✓ OK (≤3%)
35 mm²125 A97 A2.38 V (0.35%)687.6 V3.93 V (0.57%)61.9 W✓ OK (≤3%)
50 mm²151 A118 A1.67 V (0.24%)688.3 V2.75 V (0.4%)43.3 W✓ OK (≤3%)
70 mm²192 A150 A1.19 V (0.17%)688.8 V1.97 V (0.28%)31.0 W✓ OK (≤3%)
95 mm²232 A181 A0.88 V (0.13%)689.1 V1.45 V (0.21%)22.8 W✓ OK (≤3%)
120 mm²269 A210 A0.69 V (0.1%)689.3 V1.15 V (0.17%)18.1 W✓ OK (≤3%)
150 mm²309 A241 A0.56 V (0.08%)689.4 V0.92 V (0.13%)14.4 W✓ OK (≤3%)
185 mm²353 A275 A0.45 V (0.07%)689.5 V0.74 V (0.11%)11.7 W✓ OK (≤3%)
240 mm²415 A324 A0.35 V (0.05%)689.7 V0.57 V (0.08%)9.0 W✓ OK (≤3%)
300 mm²477 A372 A0.28 V (0.04%)689.7 V0.46 V (0.07%)7.2 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.03%)689.8 V0.34 V (0.05%)5.4 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 15A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 15A over 150m at 690V (voltage drop: 13.9V or 2.01%).

What is the power capacity of 15A at 690V?

At unity power factor, 15A at 690V supports 17.93 kW with a standard 15A circuit breaker.