⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

15 Amp Cable Size at 90 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 8.34V (2.01%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 8.25V (1.99%)
Voltage at Load406.7 VLine Loss: 216.7 W
Max Power & Breaker10.78 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A33.36 V (8.04%)381.6 V55.03 V (13.26%)866.7 WDrop High
2.5 mm²24 A18 A20.02 V (4.82%)395.0 V33.02 V (7.96%)520.0 W~ ≤5%
4 mm²32 A25 A12.51 V (3.01%)402.5 V20.64 V (4.97%)325.0 W~ ≤5%
6 mm²41 A32 A8.34 V (2.01%)406.7 V13.76 V (3.31%)216.7 W✓ OK (≤3%)
10 mm²57 A44 A5.0 V (1.21%)410.0 V8.25 V (1.99%)130.0 W✓ OK (≤3%)
16 mm²76 A59 A3.13 V (0.75%)411.9 V5.16 V (1.24%)81.3 W✓ OK (≤3%)
25 mm²101 A78 A2.0 V (0.48%)413.0 V3.3 V (0.8%)52.0 W✓ OK (≤3%)
35 mm²125 A97 A1.43 V (0.34%)413.6 V2.36 V (0.57%)37.1 W✓ OK (≤3%)
50 mm²151 A118 A1.0 V (0.24%)414.0 V1.65 V (0.4%)26.0 W✓ OK (≤3%)
70 mm²192 A150 A0.71 V (0.17%)414.3 V1.18 V (0.28%)18.6 W✓ OK (≤3%)
95 mm²232 A181 A0.53 V (0.13%)414.5 V0.87 V (0.21%)13.7 W✓ OK (≤3%)
120 mm²269 A210 A0.42 V (0.1%)414.6 V0.69 V (0.17%)10.8 W✓ OK (≤3%)
150 mm²309 A241 A0.33 V (0.08%)414.7 V0.55 V (0.13%)8.7 W✓ OK (≤3%)
185 mm²353 A275 A0.27 V (0.07%)414.7 V0.45 V (0.11%)7.0 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.05%)414.8 V0.34 V (0.08%)5.4 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)414.8 V0.28 V (0.07%)4.3 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)414.9 V0.21 V (0.05%)3.3 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 90 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 15A at 90 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 15A over 90m at 415V (voltage drop: 8.34V or 2.01%).

What is the power capacity of 15A at 415V?

At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.