⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

175 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 7.41V (1.07%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 9.01V (1.31%)
Voltage at Load682.6 VLine Loss: 2247.0 W
Max Power & Breaker209.15 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A345.95 V (50.14%)344.1 V570.65 V (82.7%)104860.0 WDrop High
2.5 mm²24 A18 A207.57 V (30.08%)482.4 V342.39 V (49.62%)62916.0 WDrop High
4 mm²32 A25 A129.73 V (18.8%)560.3 V213.99 V (31.01%)39322.5 WDrop High
6 mm²41 A32 A86.49 V (12.53%)603.5 V142.66 V (20.68%)26215.0 WDrop High
10 mm²57 A44 A51.89 V (7.52%)638.1 V85.6 V (12.41%)15729.0 WDrop High
16 mm²76 A59 A32.43 V (4.7%)657.6 V53.5 V (7.75%)9830.6 WDrop High
25 mm²101 A78 A20.76 V (3.01%)669.2 V34.24 V (4.96%)6291.6 WDrop High
35 mm²125 A97 A14.83 V (2.15%)675.2 V24.46 V (3.54%)4494.0 WDrop High
50 mm²151 A118 A10.38 V (1.5%)679.6 V17.12 V (2.48%)3145.8 WDrop High
70 mm²192 A150 A7.41 V (1.07%)682.6 V12.23 V (1.77%)2247.0 W✓ OK (≤3%)
95 mm²232 A181 A5.46 V (0.79%)684.5 V9.01 V (1.31%)1655.7 W✓ OK (≤3%)
120 mm²269 A210 A4.32 V (0.63%)685.7 V7.13 V (1.03%)1310.8 W✓ OK (≤3%)
150 mm²309 A241 A3.46 V (0.5%)686.5 V5.71 V (0.83%)1048.6 W✓ OK (≤3%)
185 mm²353 A275 A2.8 V (0.41%)687.2 V4.63 V (0.67%)850.2 W✓ OK (≤3%)
240 mm²415 A324 A2.16 V (0.31%)687.8 V3.57 V (0.52%)655.4 W✓ OK (≤3%)
300 mm²477 A372 A1.73 V (0.25%)688.3 V2.85 V (0.41%)524.3 W✓ OK (≤3%)
400 mm²570 A445 A1.3 V (0.19%)688.7 V2.14 V (0.31%)393.2 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 175A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 175A over 80m at 690V (voltage drop: 7.41V or 1.07%).

What is the power capacity of 175A at 690V?

At unity power factor, 175A at 690V supports 209.15 kW with a standard 175A circuit breaker.