225 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 15.36V (2.23%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 16.05V (2.33%)
Voltage at Load674.6 VLine Loss: 5987.1 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A972.98 V (141.01%)0.0 V1604.96 V (232.6%)379181.2 WDrop High
2.5 mm²24 A18 A583.79 V (84.61%)106.2 V962.98 V (139.56%)227508.7 WDrop High
4 mm²32 A25 A364.87 V (52.88%)325.1 V601.86 V (87.23%)142193.0 WDrop High
6 mm²41 A32 A243.24 V (35.25%)446.8 V401.24 V (58.15%)94795.3 WDrop High
10 mm²57 A44 A145.95 V (21.15%)544.1 V240.74 V (34.89%)56877.2 WDrop High
16 mm²76 A59 A91.22 V (13.22%)598.8 V150.47 V (21.81%)35548.2 WDrop High
25 mm²101 A78 A58.38 V (8.46%)631.6 V96.3 V (13.96%)22750.9 WDrop High
35 mm²125 A97 A41.7 V (6.04%)648.3 V68.78 V (9.97%)16250.6 WDrop High
50 mm²151 A118 A29.19 V (4.23%)660.8 V48.15 V (6.98%)11375.4 WDrop High
70 mm²192 A150 A20.85 V (3.02%)669.2 V34.39 V (4.98%)8125.3 WDrop High
95 mm²232 A181 A15.36 V (2.23%)674.6 V25.34 V (3.67%)5987.1 W✓ OK (≤3%)
120 mm²269 A210 A12.16 V (1.76%)677.8 V20.06 V (2.91%)4739.8 W✓ OK (≤3%)
150 mm²309 A241 A9.73 V (1.41%)680.3 V16.05 V (2.33%)3791.8 W✓ OK (≤3%)
185 mm²353 A275 A7.89 V (1.14%)682.1 V13.01 V (1.89%)3074.4 W✓ OK (≤3%)
240 mm²415 A324 A6.08 V (0.88%)683.9 V10.03 V (1.45%)2369.9 W✓ OK (≤3%)
300 mm²477 A372 A4.86 V (0.71%)685.1 V8.02 V (1.16%)1895.9 W✓ OK (≤3%)
400 mm²570 A445 A3.65 V (0.53%)686.4 V6.02 V (0.87%)1421.9 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 175m at 690V (voltage drop: 15.36V or 2.23%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.