225 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 17.37V (2.52%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 18.59V (2.69%)
Voltage at Load672.6 VLine Loss: 6771.1 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1389.97 V (201.45%)0.0 V2292.8 V (332.29%)541687.5 WDrop High
2.5 mm²24 A18 A833.98 V (120.87%)0.0 V1375.68 V (199.37%)325012.5 WDrop High
4 mm²32 A25 A521.24 V (75.54%)168.8 V859.8 V (124.61%)203132.8 WDrop High
6 mm²41 A32 A347.49 V (50.36%)342.5 V573.2 V (83.07%)135421.9 WDrop High
10 mm²57 A44 A208.5 V (30.22%)481.5 V343.92 V (49.84%)81253.1 WDrop High
16 mm²76 A59 A130.31 V (18.89%)559.7 V214.95 V (31.15%)50783.2 WDrop High
25 mm²101 A78 A83.4 V (12.09%)606.6 V137.57 V (19.94%)32501.2 WDrop High
35 mm²125 A97 A59.57 V (8.63%)630.4 V98.26 V (14.24%)23215.2 WDrop High
50 mm²151 A118 A41.7 V (6.04%)648.3 V68.78 V (9.97%)16250.6 WDrop High
70 mm²192 A150 A29.79 V (4.32%)660.2 V49.13 V (7.12%)11607.6 WDrop High
95 mm²232 A181 A21.95 V (3.18%)668.1 V36.2 V (5.25%)8553.0 W~ ≤5%
120 mm²269 A210 A17.37 V (2.52%)672.6 V28.66 V (4.15%)6771.1 W✓ OK (≤3%)
150 mm²309 A241 A13.9 V (2.01%)676.1 V22.93 V (3.32%)5416.9 W✓ OK (≤3%)
185 mm²353 A275 A11.27 V (1.63%)678.7 V18.59 V (2.69%)4392.1 W✓ OK (≤3%)
240 mm²415 A324 A8.69 V (1.26%)681.3 V14.33 V (2.08%)3385.5 W✓ OK (≤3%)
300 mm²477 A372 A6.95 V (1.01%)683.1 V11.46 V (1.66%)2708.4 W✓ OK (≤3%)
400 mm²570 A445 A5.21 V (0.76%)684.8 V8.6 V (1.25%)2031.3 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 225A over 250m at 690V (voltage drop: 17.37V or 2.52%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.