250 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 7.72V (1.12%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 8.26V (1.2%)
Voltage at Load682.3 VLine Loss: 3343.7 W
Max Power & Breaker298.78 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A617.76 V (89.53%)72.2 V1019.02 V (147.68%)267500.0 WDrop High
2.5 mm²24 A18 A370.66 V (53.72%)319.3 V611.41 V (88.61%)160500.0 WDrop High
4 mm²32 A25 A231.66 V (33.57%)458.3 V382.13 V (55.38%)100312.5 WDrop High
6 mm²41 A32 A154.44 V (22.38%)535.6 V254.76 V (36.92%)66875.0 WDrop High
10 mm²57 A44 A92.66 V (13.43%)597.3 V152.85 V (22.15%)40125.0 WDrop High
16 mm²76 A59 A57.92 V (8.39%)632.1 V95.53 V (13.85%)25078.1 WDrop High
25 mm²101 A78 A37.07 V (5.37%)652.9 V61.14 V (8.86%)16050.0 WDrop High
35 mm²125 A97 A26.48 V (3.84%)663.5 V43.67 V (6.33%)11464.3 WDrop High
50 mm²151 A118 A18.53 V (2.69%)671.5 V30.57 V (4.43%)8025.0 WDrop High
70 mm²192 A150 A13.24 V (1.92%)676.8 V21.84 V (3.16%)5732.1 WDrop High
95 mm²232 A181 A9.75 V (1.41%)680.2 V16.09 V (2.33%)4223.7 WDrop High
120 mm²269 A210 A7.72 V (1.12%)682.3 V12.74 V (1.85%)3343.7 W✓ OK (≤3%)
150 mm²309 A241 A6.18 V (0.9%)683.8 V10.19 V (1.48%)2675.0 W✓ OK (≤3%)
185 mm²353 A275 A5.01 V (0.73%)685.0 V8.26 V (1.2%)2168.9 W✓ OK (≤3%)
240 mm²415 A324 A3.86 V (0.56%)686.1 V6.37 V (0.92%)1671.9 W✓ OK (≤3%)
300 mm²477 A372 A3.09 V (0.45%)686.9 V5.1 V (0.74%)1337.5 W✓ OK (≤3%)
400 mm²570 A445 A2.32 V (0.34%)687.7 V3.82 V (0.55%)1003.1 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 250A at 100 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 100m at 690V (voltage drop: 7.72V or 1.12%).

What is the power capacity of 250A at 690V?

At unity power factor, 250A at 690V supports 298.78 kW with a standard 250A circuit breaker.