250 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 13.51V (1.96%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 14.46V (2.1%)
Voltage at Load676.5 VLine Loss: 5851.6 W
Max Power & Breaker298.78 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1081.09 V (156.68%)0.0 V1783.29 V (258.45%)468125.0 WDrop High
2.5 mm²24 A18 A648.65 V (94.01%)41.3 V1069.97 V (155.07%)280875.0 WDrop High
4 mm²32 A25 A405.41 V (58.75%)284.6 V668.73 V (96.92%)175546.9 WDrop High
6 mm²41 A32 A270.27 V (39.17%)419.7 V445.82 V (64.61%)117031.2 WDrop High
10 mm²57 A44 A162.16 V (23.5%)527.8 V267.49 V (38.77%)70218.7 WDrop High
16 mm²76 A59 A101.35 V (14.69%)588.6 V167.18 V (24.23%)43886.7 WDrop High
25 mm²101 A78 A64.87 V (9.4%)625.1 V107.0 V (15.51%)28087.5 WDrop High
35 mm²125 A97 A46.33 V (6.71%)643.7 V76.43 V (11.08%)20062.5 WDrop High
50 mm²151 A118 A32.43 V (4.7%)657.6 V53.5 V (7.75%)14043.7 WDrop High
70 mm²192 A150 A23.17 V (3.36%)666.8 V38.21 V (5.54%)10031.2 WDrop High
95 mm²232 A181 A17.07 V (2.47%)672.9 V28.16 V (4.08%)7391.4 WDrop High
120 mm²269 A210 A13.51 V (1.96%)676.5 V22.29 V (3.23%)5851.6 W✓ OK (≤3%)
150 mm²309 A241 A10.81 V (1.57%)679.2 V17.83 V (2.58%)4681.2 W✓ OK (≤3%)
185 mm²353 A275 A8.77 V (1.27%)681.2 V14.46 V (2.1%)3795.6 W✓ OK (≤3%)
240 mm²415 A324 A6.76 V (0.98%)683.2 V11.15 V (1.62%)2925.8 W✓ OK (≤3%)
300 mm²477 A372 A5.41 V (0.78%)684.6 V8.92 V (1.29%)2340.6 W✓ OK (≤3%)
400 mm²570 A445 A4.05 V (0.59%)685.9 V6.69 V (0.97%)1755.5 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 250A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 175m at 690V (voltage drop: 13.51V or 1.96%).

What is the power capacity of 250A at 690V?

At unity power factor, 250A at 690V supports 298.78 kW with a standard 250A circuit breaker.