250 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 19.31V (2.8%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.11V (2.77%)
Voltage at Load670.7 VLine Loss: 8359.4 W
Max Power & Breaker298.78 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3088.82 V (447.66%)0.0 V5095.12 V (738.42%)1337500.0 WDrop High
2.5 mm²24 A18 A1853.29 V (268.59%)0.0 V3057.07 V (443.05%)802500.0 WDrop High
4 mm²32 A25 A1158.31 V (167.87%)0.0 V1910.67 V (276.91%)501562.5 WDrop High
6 mm²41 A32 A772.21 V (111.91%)0.0 V1273.78 V (184.61%)334375.0 WDrop High
10 mm²57 A44 A463.32 V (67.15%)226.7 V764.27 V (110.76%)200625.0 WDrop High
16 mm²76 A59 A289.58 V (41.97%)400.4 V477.67 V (69.23%)125390.6 WDrop High
25 mm²101 A78 A185.33 V (26.86%)504.7 V305.71 V (44.31%)80250.0 WDrop High
35 mm²125 A97 A132.38 V (19.19%)557.6 V218.36 V (31.65%)57321.4 WDrop High
50 mm²151 A118 A92.66 V (13.43%)597.3 V152.85 V (22.15%)40125.0 WDrop High
70 mm²192 A150 A66.19 V (9.59%)623.8 V109.18 V (15.82%)28660.7 WDrop High
95 mm²232 A181 A48.77 V (7.07%)641.2 V80.45 V (11.66%)21118.4 WDrop High
120 mm²269 A210 A38.61 V (5.6%)651.4 V63.69 V (9.23%)16718.8 WDrop High
150 mm²309 A241 A30.89 V (4.48%)659.1 V50.95 V (7.38%)13375.0 W~ ≤5%
185 mm²353 A275 A25.04 V (3.63%)665.0 V41.31 V (5.99%)10844.6 W~ ≤5%
240 mm²415 A324 A19.31 V (2.8%)670.7 V31.84 V (4.62%)8359.4 W✓ OK (≤3%)
300 mm²477 A372 A15.44 V (2.24%)674.6 V25.48 V (3.69%)6687.5 W✓ OK (≤3%)
400 mm²570 A445 A11.58 V (1.68%)678.4 V19.11 V (2.77%)5015.6 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 250A at 500 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 250A over 500m at 690V (voltage drop: 19.31V or 2.8%).

What is the power capacity of 250A at 690V?

At unity power factor, 250A at 690V supports 298.78 kW with a standard 250A circuit breaker.