30 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 11.12V (2.68%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 11.46V (2.76%)
Voltage at Load403.9 VLine Loss: 577.8 W
Max Power & Breaker21.56 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.13 V (17.86%)340.9 V122.28 V (29.47%)3852.0 WDrop High
2.5 mm²24 A18 A44.48 V (10.72%)370.5 V73.37 V (17.68%)2311.2 WDrop High
4 mm²32 A25 A27.8 V (6.7%)387.2 V45.86 V (11.05%)1444.5 WDrop High
6 mm²41 A32 A18.53 V (4.47%)396.5 V30.57 V (7.37%)963.0 W~ ≤5%
10 mm²57 A44 A11.12 V (2.68%)403.9 V18.34 V (4.42%)577.8 W✓ OK (≤3%)
16 mm²76 A59 A6.95 V (1.67%)408.1 V11.46 V (2.76%)361.1 W✓ OK (≤3%)
25 mm²101 A78 A4.45 V (1.07%)410.6 V7.34 V (1.77%)231.1 W✓ OK (≤3%)
35 mm²125 A97 A3.18 V (0.77%)411.8 V5.24 V (1.26%)165.1 W✓ OK (≤3%)
50 mm²151 A118 A2.22 V (0.54%)412.8 V3.67 V (0.88%)115.6 W✓ OK (≤3%)
70 mm²192 A150 A1.59 V (0.38%)413.4 V2.62 V (0.63%)82.5 W✓ OK (≤3%)
95 mm²232 A181 A1.17 V (0.28%)413.8 V1.93 V (0.47%)60.8 W✓ OK (≤3%)
120 mm²269 A210 A0.93 V (0.22%)414.1 V1.53 V (0.37%)48.1 W✓ OK (≤3%)
150 mm²309 A241 A0.74 V (0.18%)414.3 V1.22 V (0.29%)38.5 W✓ OK (≤3%)
185 mm²353 A275 A0.6 V (0.14%)414.4 V0.99 V (0.24%)31.2 W✓ OK (≤3%)
240 mm²415 A324 A0.46 V (0.11%)414.5 V0.76 V (0.18%)24.1 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.09%)414.6 V0.61 V (0.15%)19.3 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.07%)414.7 V0.46 V (0.11%)14.4 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 30A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 30A over 100m at 415V (voltage drop: 11.12V or 2.68%).

What is the power capacity of 30A at 415V?

At unity power factor, 30A at 415V supports 21.56 kW with a standard 30A circuit breaker.