⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

30 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 1.35V (2.82%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.41V (2.94%)
Voltage at Load46.6 VLine Loss: 40.5 W
Max Power & Breaker1.44 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A85.6 V (178.33%)0.0 V141.2 V (294.17%)2568.0 WDrop High
2.5 mm²24 A18 A51.36 V (107.0%)0.0 V84.72 V (176.5%)1540.8 WDrop High
4 mm²32 A25 A32.1 V (66.87%)15.9 V52.95 V (110.31%)963.0 WDrop High
6 mm²41 A32 A21.4 V (44.58%)26.6 V35.3 V (73.54%)642.0 WDrop High
10 mm²57 A44 A12.84 V (26.75%)35.2 V21.18 V (44.12%)385.2 WDrop High
16 mm²76 A59 A8.02 V (16.72%)40.0 V13.24 V (27.58%)240.7 WDrop High
25 mm²101 A78 A5.14 V (10.7%)42.9 V8.47 V (17.65%)154.1 WDrop High
35 mm²125 A97 A3.67 V (7.64%)44.3 V6.05 V (12.61%)110.1 WDrop High
50 mm²151 A118 A2.57 V (5.35%)45.4 V4.24 V (8.82%)77.0 WDrop High
70 mm²192 A150 A1.83 V (3.82%)46.2 V3.03 V (6.3%)55.0 W~ ≤5%
95 mm²232 A181 A1.35 V (2.82%)46.6 V2.23 V (4.64%)40.5 W✓ OK (≤3%)
120 mm²269 A210 A1.07 V (2.23%)46.9 V1.76 V (3.68%)32.1 W✓ OK (≤3%)
150 mm²309 A241 A0.86 V (1.78%)47.1 V1.41 V (2.94%)25.7 W✓ OK (≤3%)
185 mm²353 A275 A0.69 V (1.45%)47.3 V1.14 V (2.39%)20.8 W✓ OK (≤3%)
240 mm²415 A324 A0.53 V (1.11%)47.5 V0.88 V (1.84%)16.0 W✓ OK (≤3%)
300 mm²477 A372 A0.43 V (0.89%)47.6 V0.71 V (1.47%)12.8 W✓ OK (≤3%)
400 mm²570 A445 A0.32 V (0.67%)47.7 V0.53 V (1.1%)9.6 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 30A at 100 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 30A over 100m at 48V (voltage drop: 1.35V or 2.82%).

What is the power capacity of 30A at 48V?

At unity power factor, 30A at 48V supports 1.44 kW with a standard 30A circuit breaker.