30 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 16.68V (2.42%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 17.2V (2.49%)
Voltage at Load673.3 VLine Loss: 866.7 W
Max Power & Breaker35.85 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A111.2 V (16.12%)578.8 V183.42 V (26.58%)5778.0 WDrop High
2.5 mm²24 A18 A66.72 V (9.67%)623.3 V110.05 V (15.95%)3466.8 WDrop High
4 mm²32 A25 A41.7 V (6.04%)648.3 V68.78 V (9.97%)2166.8 WDrop High
6 mm²41 A32 A27.8 V (4.03%)662.2 V45.86 V (6.65%)1444.5 W~ ≤5%
10 mm²57 A44 A16.68 V (2.42%)673.3 V27.51 V (3.99%)866.7 W✓ OK (≤3%)
16 mm²76 A59 A10.42 V (1.51%)679.6 V17.2 V (2.49%)541.7 W✓ OK (≤3%)
25 mm²101 A78 A6.67 V (0.97%)683.3 V11.01 V (1.59%)346.7 W✓ OK (≤3%)
35 mm²125 A97 A4.77 V (0.69%)685.2 V7.86 V (1.14%)247.6 W✓ OK (≤3%)
50 mm²151 A118 A3.34 V (0.48%)686.7 V5.5 V (0.8%)173.3 W✓ OK (≤3%)
70 mm²192 A150 A2.38 V (0.35%)687.6 V3.93 V (0.57%)123.8 W✓ OK (≤3%)
95 mm²232 A181 A1.76 V (0.25%)688.2 V2.9 V (0.42%)91.2 W✓ OK (≤3%)
120 mm²269 A210 A1.39 V (0.2%)688.6 V2.29 V (0.33%)72.2 W✓ OK (≤3%)
150 mm²309 A241 A1.11 V (0.16%)688.9 V1.83 V (0.27%)57.8 W✓ OK (≤3%)
185 mm²353 A275 A0.9 V (0.13%)689.1 V1.49 V (0.22%)46.8 W✓ OK (≤3%)
240 mm²415 A324 A0.69 V (0.1%)689.3 V1.15 V (0.17%)36.1 W✓ OK (≤3%)
300 mm²477 A372 A0.56 V (0.08%)689.4 V0.92 V (0.13%)28.9 W✓ OK (≤3%)
400 mm²570 A445 A0.42 V (0.06%)689.6 V0.69 V (0.1%)21.7 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 30A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 30A over 150m at 690V (voltage drop: 16.68V or 2.42%).

What is the power capacity of 30A at 690V?

At unity power factor, 30A at 690V supports 35.85 kW with a standard 30A circuit breaker.