325 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.65V (0.16%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.66V (0.16%)
Voltage at Load414.3 VLine Loss: 366.5 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A80.31 V (19.35%)334.7 V132.47 V (31.92%)45207.5 WDrop High
2.5 mm²24 A18 A48.19 V (11.61%)366.8 V79.48 V (19.15%)27124.5 WDrop High
4 mm²32 A25 A30.12 V (7.26%)384.9 V49.68 V (11.97%)16952.8 WDrop High
6 mm²41 A32 A20.08 V (4.84%)394.9 V33.12 V (7.98%)11301.9 WDrop High
10 mm²57 A44 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 WDrop High
16 mm²76 A59 A7.53 V (1.81%)407.5 V12.42 V (2.99%)4238.2 WDrop High
25 mm²101 A78 A4.82 V (1.16%)410.2 V7.95 V (1.92%)2712.4 WDrop High
35 mm²125 A97 A3.44 V (0.83%)411.6 V5.68 V (1.37%)1937.5 WDrop High
50 mm²151 A118 A2.41 V (0.58%)412.6 V3.97 V (0.96%)1356.2 WDrop High
70 mm²192 A150 A1.72 V (0.41%)413.3 V2.84 V (0.68%)968.7 WDrop High
95 mm²232 A181 A1.27 V (0.31%)413.7 V2.09 V (0.5%)713.8 WDrop High
120 mm²269 A210 A1.0 V (0.24%)414.0 V1.66 V (0.4%)565.1 WDrop High
150 mm²309 A241 A0.8 V (0.19%)414.2 V1.32 V (0.32%)452.1 WDrop High
185 mm²353 A275 A0.65 V (0.16%)414.3 V1.07 V (0.26%)366.5 W✓ OK (≤3%)
240 mm²415 A324 A0.5 V (0.12%)414.5 V0.83 V (0.2%)282.5 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.1%)414.6 V0.66 V (0.16%)226.0 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.07%)414.7 V0.5 V (0.12%)169.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 10 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 10m at 415V (voltage drop: 0.65V or 0.16%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.