325 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.63V (0.39%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.66V (0.4%)
Voltage at Load413.4 VLine Loss: 916.4 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A200.77 V (48.38%)214.2 V331.18 V (79.8%)113018.7 WDrop High
2.5 mm²24 A18 A120.46 V (29.03%)294.5 V198.71 V (47.88%)67811.2 WDrop High
4 mm²32 A25 A75.29 V (18.14%)339.7 V124.19 V (29.93%)42382.0 WDrop High
6 mm²41 A32 A50.19 V (12.09%)364.8 V82.8 V (19.95%)28254.7 WDrop High
10 mm²57 A44 A30.12 V (7.26%)384.9 V49.68 V (11.97%)16952.8 WDrop High
16 mm²76 A59 A18.82 V (4.54%)396.2 V31.05 V (7.48%)10595.5 WDrop High
25 mm²101 A78 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 WDrop High
35 mm²125 A97 A8.6 V (2.07%)406.4 V14.19 V (3.42%)4843.7 WDrop High
50 mm²151 A118 A6.02 V (1.45%)409.0 V9.94 V (2.39%)3390.6 WDrop High
70 mm²192 A150 A4.3 V (1.04%)410.7 V7.1 V (1.71%)2421.8 WDrop High
95 mm²232 A181 A3.17 V (0.76%)411.8 V5.23 V (1.26%)1784.5 WDrop High
120 mm²269 A210 A2.51 V (0.6%)412.5 V4.14 V (1.0%)1412.7 WDrop High
150 mm²309 A241 A2.01 V (0.48%)413.0 V3.31 V (0.8%)1130.2 WDrop High
185 mm²353 A275 A1.63 V (0.39%)413.4 V2.69 V (0.65%)916.4 W✓ OK (≤3%)
240 mm²415 A324 A1.25 V (0.3%)413.7 V2.07 V (0.5%)706.4 W✓ OK (≤3%)
300 mm²477 A372 A1.0 V (0.24%)414.0 V1.66 V (0.4%)565.1 W✓ OK (≤3%)
400 mm²570 A445 A0.75 V (0.18%)414.2 V1.24 V (0.3%)423.8 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 25m at 415V (voltage drop: 1.63V or 0.39%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.