325 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 25 m (82.0 ft).
Copper Cable (≤3% Drop)185 mm²Drop: 1.63V (0.39%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.66V (0.4%)
Voltage at Load413.4 VLine Loss: 916.4 W
Max Power & Breaker233.61 kW350A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 200.77 V (48.38%) | 214.2 V | 331.18 V (79.8%) | 113018.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 120.46 V (29.03%) | 294.5 V | 198.71 V (47.88%) | 67811.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 75.29 V (18.14%) | 339.7 V | 124.19 V (29.93%) | 42382.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 50.19 V (12.09%) | 364.8 V | 82.8 V (19.95%) | 28254.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 30.12 V (7.26%) | 384.9 V | 49.68 V (11.97%) | 16952.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 18.82 V (4.54%) | 396.2 V | 31.05 V (7.48%) | 10595.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 12.05 V (2.9%) | 403.0 V | 19.87 V (4.79%) | 6781.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 8.6 V (2.07%) | 406.4 V | 14.19 V (3.42%) | 4843.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 6.02 V (1.45%) | 409.0 V | 9.94 V (2.39%) | 3390.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 4.3 V (1.04%) | 410.7 V | 7.1 V (1.71%) | 2421.8 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.17 V (0.76%) | 411.8 V | 5.23 V (1.26%) | 1784.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 2.51 V (0.6%) | 412.5 V | 4.14 V (1.0%) | 1412.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.01 V (0.48%) | 413.0 V | 3.31 V (0.8%) | 1130.2 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.63 V (0.39%) | 413.4 V | 2.69 V (0.65%) | 916.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.25 V (0.3%) | 413.7 V | 2.07 V (0.5%) | 706.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.0 V (0.24%) | 414.0 V | 1.66 V (0.4%) | 565.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.75 V (0.18%) | 414.2 V | 1.24 V (0.3%) | 423.8 W | ✓ OK (≤3%) |
FAQ — 325 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 325A at 25 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 25m at 415V (voltage drop: 1.63V or 0.39%).
What is the power capacity of 325A at 415V?
At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.
Related Lengths & Currents (415V)
325A · 5m (415V)325A · 10m (415V)325A · 15m (415V)325A · 20m (415V)325A · 30m (415V)325A · 35m (415V)325A · 40m (415V)325A · 45m (415V)325A · 50m (415V)325A · 60m (415V)325A · 70m (415V)10A · 25m (415V)16A · 25m (415V)20A · 25m (415V)25A · 25m (415V)32A · 25m (415V)40A · 25m (415V)50A · 25m (415V)63A · 25m (415V)80A · 25m (415V)100A · 25m (415V)125A · 25m (415V)160A · 25m (415V)200A · 25m (415V)