⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 30 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.95V (0.47%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.99V (0.48%)
Voltage at Load413.0 VLine Loss: 1099.6 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A240.93 V (58.06%)174.1 V397.42 V (95.76%)135622.5 WDrop High
2.5 mm²24 A18 A144.56 V (34.83%)270.4 V238.45 V (57.46%)81373.5 WDrop High
4 mm²32 A25 A90.35 V (21.77%)324.7 V149.03 V (35.91%)50858.4 WDrop High
6 mm²41 A32 A60.23 V (14.51%)354.8 V99.35 V (23.94%)33905.6 WDrop High
10 mm²57 A44 A36.14 V (8.71%)378.9 V59.61 V (14.36%)20343.4 WDrop High
16 mm²76 A59 A22.59 V (5.44%)392.4 V37.26 V (8.98%)12714.6 WDrop High
25 mm²101 A78 A14.46 V (3.48%)400.5 V23.85 V (5.75%)8137.4 WDrop High
35 mm²125 A97 A10.33 V (2.49%)404.7 V17.03 V (4.1%)5812.4 WDrop High
50 mm²151 A118 A7.23 V (1.74%)407.8 V11.92 V (2.87%)4068.7 WDrop High
70 mm²192 A150 A5.16 V (1.24%)409.8 V8.52 V (2.05%)2906.2 WDrop High
95 mm²232 A181 A3.8 V (0.92%)411.2 V6.28 V (1.51%)2141.4 WDrop High
120 mm²269 A210 A3.01 V (0.73%)412.0 V4.97 V (1.2%)1695.3 WDrop High
150 mm²309 A241 A2.41 V (0.58%)412.6 V3.97 V (0.96%)1356.2 WDrop High
185 mm²353 A275 A1.95 V (0.47%)413.0 V3.22 V (0.78%)1099.6 W✓ OK (≤3%)
240 mm²415 A324 A1.51 V (0.36%)413.5 V2.48 V (0.6%)847.6 W✓ OK (≤3%)
300 mm²477 A372 A1.2 V (0.29%)413.8 V1.99 V (0.48%)678.1 W✓ OK (≤3%)
400 mm²570 A445 A0.9 V (0.22%)414.1 V1.49 V (0.36%)508.6 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 30 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 30 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 30m at 415V (voltage drop: 1.95V or 0.47%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.