325 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.3V (0.31%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.32V (0.32%)
Voltage at Load413.7 VLine Loss: 733.1 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A160.62 V (38.7%)254.4 V264.95 V (63.84%)90415.0 WDrop High
2.5 mm²24 A18 A96.37 V (23.22%)318.6 V158.97 V (38.31%)54249.0 WDrop High
4 mm²32 A25 A60.23 V (14.51%)354.8 V99.35 V (23.94%)33905.6 WDrop High
6 mm²41 A32 A40.15 V (9.68%)374.8 V66.24 V (15.96%)22603.8 WDrop High
10 mm²57 A44 A24.09 V (5.81%)390.9 V39.74 V (9.58%)13562.2 WDrop High
16 mm²76 A59 A15.06 V (3.63%)399.9 V24.84 V (5.99%)8476.4 WDrop High
25 mm²101 A78 A9.64 V (2.32%)405.4 V15.9 V (3.83%)5424.9 WDrop High
35 mm²125 A97 A6.88 V (1.66%)408.1 V11.35 V (2.74%)3874.9 WDrop High
50 mm²151 A118 A4.82 V (1.16%)410.2 V7.95 V (1.92%)2712.4 WDrop High
70 mm²192 A150 A3.44 V (0.83%)411.6 V5.68 V (1.37%)1937.5 WDrop High
95 mm²232 A181 A2.54 V (0.61%)412.5 V4.18 V (1.01%)1427.6 WDrop High
120 mm²269 A210 A2.01 V (0.48%)413.0 V3.31 V (0.8%)1130.2 WDrop High
150 mm²309 A241 A1.61 V (0.39%)413.4 V2.65 V (0.64%)904.1 WDrop High
185 mm²353 A275 A1.3 V (0.31%)413.7 V2.15 V (0.52%)733.1 W✓ OK (≤3%)
240 mm²415 A324 A1.0 V (0.24%)414.0 V1.66 V (0.4%)565.1 W✓ OK (≤3%)
300 mm²477 A372 A0.8 V (0.19%)414.2 V1.32 V (0.32%)452.1 W✓ OK (≤3%)
400 mm²570 A445 A0.6 V (0.15%)414.4 V0.99 V (0.24%)339.1 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 20m at 415V (voltage drop: 1.3V or 0.31%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.