325 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.33V (0.08%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.33V (0.08%)
Voltage at Load414.7 VLine Loss: 183.3 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A40.15 V (9.68%)374.8 V66.24 V (15.96%)22603.8 WDrop High
2.5 mm²24 A18 A24.09 V (5.81%)390.9 V39.74 V (9.58%)13562.2 WDrop High
4 mm²32 A25 A15.06 V (3.63%)399.9 V24.84 V (5.99%)8476.4 WDrop High
6 mm²41 A32 A10.04 V (2.42%)405.0 V16.56 V (3.99%)5650.9 WDrop High
10 mm²57 A44 A6.02 V (1.45%)409.0 V9.94 V (2.39%)3390.6 WDrop High
16 mm²76 A59 A3.76 V (0.91%)411.2 V6.21 V (1.5%)2119.1 WDrop High
25 mm²101 A78 A2.41 V (0.58%)412.6 V3.97 V (0.96%)1356.2 WDrop High
35 mm²125 A97 A1.72 V (0.41%)413.3 V2.84 V (0.68%)968.7 WDrop High
50 mm²151 A118 A1.2 V (0.29%)413.8 V1.99 V (0.48%)678.1 WDrop High
70 mm²192 A150 A0.86 V (0.21%)414.1 V1.42 V (0.34%)484.4 WDrop High
95 mm²232 A181 A0.63 V (0.15%)414.4 V1.05 V (0.25%)356.9 WDrop High
120 mm²269 A210 A0.5 V (0.12%)414.5 V0.83 V (0.2%)282.5 WDrop High
150 mm²309 A241 A0.4 V (0.1%)414.6 V0.66 V (0.16%)226.0 WDrop High
185 mm²353 A275 A0.33 V (0.08%)414.7 V0.54 V (0.13%)183.3 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.06%)414.7 V0.41 V (0.1%)141.3 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.05%)414.8 V0.33 V (0.08%)113.0 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)414.8 V0.25 V (0.06%)84.8 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 5m at 415V (voltage drop: 0.33V or 0.08%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.