325 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 3.26V (0.78%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.31V (0.8%)
Voltage at Load411.7 VLine Loss: 1832.7 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A401.55 V (96.76%)13.5 V662.37 V (159.61%)226037.5 WDrop High
2.5 mm²24 A18 A240.93 V (58.06%)174.1 V397.42 V (95.76%)135622.5 WDrop High
4 mm²32 A25 A150.58 V (36.28%)264.4 V248.39 V (59.85%)84764.1 WDrop High
6 mm²41 A32 A100.39 V (24.19%)314.6 V165.59 V (39.9%)56509.4 WDrop High
10 mm²57 A44 A60.23 V (14.51%)354.8 V99.35 V (23.94%)33905.6 WDrop High
16 mm²76 A59 A37.65 V (9.07%)377.4 V62.1 V (14.96%)21191.0 WDrop High
25 mm²101 A78 A24.09 V (5.81%)390.9 V39.74 V (9.58%)13562.2 WDrop High
35 mm²125 A97 A17.21 V (4.15%)397.8 V28.39 V (6.84%)9687.3 WDrop High
50 mm²151 A118 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 WDrop High
70 mm²192 A150 A8.6 V (2.07%)406.4 V14.19 V (3.42%)4843.7 WDrop High
95 mm²232 A181 A6.34 V (1.53%)408.7 V10.46 V (2.52%)3569.0 WDrop High
120 mm²269 A210 A5.02 V (1.21%)410.0 V8.28 V (2.0%)2825.5 WDrop High
150 mm²309 A241 A4.02 V (0.97%)411.0 V6.62 V (1.6%)2260.4 WDrop High
185 mm²353 A275 A3.26 V (0.78%)411.7 V5.37 V (1.29%)1832.7 W✓ OK (≤3%)
240 mm²415 A324 A2.51 V (0.6%)412.5 V4.14 V (1.0%)1412.7 W✓ OK (≤3%)
300 mm²477 A372 A2.01 V (0.48%)413.0 V3.31 V (0.8%)1130.2 W✓ OK (≤3%)
400 mm²570 A445 A1.51 V (0.36%)413.5 V2.48 V (0.6%)847.6 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 50m at 415V (voltage drop: 3.26V or 0.78%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.