325 Amp Cable Size at 150 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 1.3V (2.72%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.6V (17.93%)
Voltage at Load46.7 VLine Loss: 423.8 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1391.0 V (2897.92%)0.0 V2294.5 V (4780.21%)452075.0 WDrop High
2.5 mm²24 A18 A834.6 V (1738.75%)0.0 V1376.7 V (2868.12%)271245.0 WDrop High
4 mm²32 A25 A521.62 V (1086.72%)0.0 V860.44 V (1792.58%)169528.1 WDrop High
6 mm²41 A32 A347.75 V (724.48%)0.0 V573.62 V (1195.05%)113018.8 WDrop High
10 mm²57 A44 A208.65 V (434.69%)0.0 V344.17 V (717.03%)67811.2 WDrop High
16 mm²76 A59 A130.41 V (271.68%)0.0 V215.11 V (448.14%)42382.0 WDrop High
25 mm²101 A78 A83.46 V (173.87%)0.0 V137.67 V (286.81%)27124.5 WDrop High
35 mm²125 A97 A59.61 V (124.2%)0.0 V98.34 V (204.87%)19374.6 WDrop High
50 mm²151 A118 A41.73 V (86.94%)6.3 V68.83 V (143.41%)13562.2 WDrop High
70 mm²192 A150 A29.81 V (62.1%)18.2 V49.17 V (102.43%)9687.3 WDrop High
95 mm²232 A181 A21.96 V (45.76%)26.0 V36.23 V (75.48%)7138.0 WDrop High
120 mm²269 A210 A17.39 V (36.22%)30.6 V28.68 V (59.75%)5650.9 WDrop High
150 mm²309 A241 A13.91 V (28.98%)34.1 V22.95 V (47.8%)4520.8 WDrop High
185 mm²353 A275 A11.28 V (23.5%)36.7 V18.6 V (38.76%)3665.5 WDrop High
240 mm²415 A324 A8.69 V (18.11%)39.3 V14.34 V (29.88%)2825.5 WDrop High
300 mm²477 A372 A6.96 V (14.49%)41.0 V11.47 V (23.9%)2260.4 WDrop High
400 mm²570 A445 A5.22 V (10.87%)42.8 V8.6 V (17.93%)1695.3 WDrop High

FAQ — 325 Amp Cable Size at 150 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 150 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 325A over 150m at 48V (voltage drop: 1.3V or 2.72%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.