325 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 9.77V (1.42%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 9.94V (1.44%)
Voltage at Load680.2 VLine Loss: 5498.2 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1204.64 V (174.59%)0.0 V1987.1 V (287.98%)678112.5 WDrop High
2.5 mm²24 A18 A722.78 V (104.75%)0.0 V1192.26 V (172.79%)406867.5 WDrop High
4 mm²32 A25 A451.74 V (65.47%)238.3 V745.16 V (107.99%)254292.2 WDrop High
6 mm²41 A32 A301.16 V (43.65%)388.8 V496.77 V (72.0%)169528.1 WDrop High
10 mm²57 A44 A180.7 V (26.19%)509.3 V298.06 V (43.2%)101716.9 WDrop High
16 mm²76 A59 A112.94 V (16.37%)577.1 V186.29 V (27.0%)63573.0 WDrop High
25 mm²101 A78 A72.28 V (10.48%)617.7 V119.23 V (17.28%)40686.7 WDrop High
35 mm²125 A97 A51.63 V (7.48%)638.4 V85.16 V (12.34%)29062.0 WDrop High
50 mm²151 A118 A36.14 V (5.24%)653.9 V59.61 V (8.64%)20343.4 WDrop High
70 mm²192 A150 A25.81 V (3.74%)664.2 V42.58 V (6.17%)14531.0 WDrop High
95 mm²232 A181 A19.02 V (2.76%)671.0 V31.38 V (4.55%)10707.0 WDrop High
120 mm²269 A210 A15.06 V (2.18%)674.9 V24.84 V (3.6%)8476.4 WDrop High
150 mm²309 A241 A12.05 V (1.75%)678.0 V19.87 V (2.88%)6781.1 WDrop High
185 mm²353 A275 A9.77 V (1.42%)680.2 V16.11 V (2.34%)5498.2 W✓ OK (≤3%)
240 mm²415 A324 A7.53 V (1.09%)682.5 V12.42 V (1.8%)4238.2 W✓ OK (≤3%)
300 mm²477 A372 A6.02 V (0.87%)684.0 V9.94 V (1.44%)3390.6 W✓ OK (≤3%)
400 mm²570 A445 A4.52 V (0.65%)685.5 V7.45 V (1.08%)2542.9 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 150m at 690V (voltage drop: 9.77V or 1.42%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.