325 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 2.6V (0.38%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 2.65V (0.38%)
Voltage at Load687.4 VLine Loss: 1466.2 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A321.24 V (46.56%)368.8 V529.89 V (76.8%)180830.0 WDrop High
2.5 mm²24 A18 A192.74 V (27.93%)497.3 V317.94 V (46.08%)108498.0 WDrop High
4 mm²32 A25 A120.46 V (17.46%)569.5 V198.71 V (28.8%)67811.2 WDrop High
6 mm²41 A32 A80.31 V (11.64%)609.7 V132.47 V (19.2%)45207.5 WDrop High
10 mm²57 A44 A48.19 V (6.98%)641.8 V79.48 V (11.52%)27124.5 WDrop High
16 mm²76 A59 A30.12 V (4.36%)659.9 V49.68 V (7.2%)16952.8 WDrop High
25 mm²101 A78 A19.27 V (2.79%)670.7 V31.79 V (4.61%)10849.8 WDrop High
35 mm²125 A97 A13.77 V (2.0%)676.2 V22.71 V (3.29%)7749.9 WDrop High
50 mm²151 A118 A9.64 V (1.4%)680.4 V15.9 V (2.3%)5424.9 WDrop High
70 mm²192 A150 A6.88 V (1.0%)683.1 V11.35 V (1.65%)3874.9 WDrop High
95 mm²232 A181 A5.07 V (0.74%)684.9 V8.37 V (1.21%)2855.2 WDrop High
120 mm²269 A210 A4.02 V (0.58%)686.0 V6.62 V (0.96%)2260.4 WDrop High
150 mm²309 A241 A3.21 V (0.47%)686.8 V5.3 V (0.77%)1808.3 WDrop High
185 mm²353 A275 A2.6 V (0.38%)687.4 V4.3 V (0.62%)1466.2 W✓ OK (≤3%)
240 mm²415 A324 A2.01 V (0.29%)688.0 V3.31 V (0.48%)1130.2 W✓ OK (≤3%)
300 mm²477 A372 A1.61 V (0.23%)688.4 V2.65 V (0.38%)904.1 W✓ OK (≤3%)
400 mm²570 A445 A1.2 V (0.17%)688.8 V1.99 V (0.29%)678.1 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 40 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 40m at 690V (voltage drop: 2.6V or 0.38%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.