⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.98V (0.14%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.99V (0.14%)
Voltage at Load689.0 VLine Loss: 549.8 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A120.46 V (17.46%)569.5 V198.71 V (28.8%)67811.2 WDrop High
2.5 mm²24 A18 A72.28 V (10.48%)617.7 V119.23 V (17.28%)40686.8 WDrop High
4 mm²32 A25 A45.17 V (6.55%)644.8 V74.52 V (10.8%)25429.2 WDrop High
6 mm²41 A32 A30.12 V (4.36%)659.9 V49.68 V (7.2%)16952.8 WDrop High
10 mm²57 A44 A18.07 V (2.62%)671.9 V29.81 V (4.32%)10171.7 WDrop High
16 mm²76 A59 A11.29 V (1.64%)678.7 V18.63 V (2.7%)6357.3 WDrop High
25 mm²101 A78 A7.23 V (1.05%)682.8 V11.92 V (1.73%)4068.7 WDrop High
35 mm²125 A97 A5.16 V (0.75%)684.8 V8.52 V (1.23%)2906.2 WDrop High
50 mm²151 A118 A3.61 V (0.52%)686.4 V5.96 V (0.86%)2034.3 WDrop High
70 mm²192 A150 A2.58 V (0.37%)687.4 V4.26 V (0.62%)1453.1 WDrop High
95 mm²232 A181 A1.9 V (0.28%)688.1 V3.14 V (0.45%)1070.7 WDrop High
120 mm²269 A210 A1.51 V (0.22%)688.5 V2.48 V (0.36%)847.6 WDrop High
150 mm²309 A241 A1.2 V (0.17%)688.8 V1.99 V (0.29%)678.1 WDrop High
185 mm²353 A275 A0.98 V (0.14%)689.0 V1.61 V (0.23%)549.8 W✓ OK (≤3%)
240 mm²415 A324 A0.75 V (0.11%)689.2 V1.24 V (0.18%)423.8 W✓ OK (≤3%)
300 mm²477 A372 A0.6 V (0.09%)689.4 V0.99 V (0.14%)339.1 W✓ OK (≤3%)
400 mm²570 A445 A0.45 V (0.07%)689.5 V0.75 V (0.11%)254.3 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 15m at 690V (voltage drop: 0.98V or 0.14%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.