325 Amp Cable Size at 60 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 3.91V (0.57%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.97V (0.58%)
Voltage at Load686.1 VLine Loss: 2199.3 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A481.86 V (69.83%)208.1 V794.84 V (115.19%)271245.0 WDrop High
2.5 mm²24 A18 A289.11 V (41.9%)400.9 V476.9 V (69.12%)162747.0 WDrop High
4 mm²32 A25 A180.7 V (26.19%)509.3 V298.06 V (43.2%)101716.9 WDrop High
6 mm²41 A32 A120.46 V (17.46%)569.5 V198.71 V (28.8%)67811.2 WDrop High
10 mm²57 A44 A72.28 V (10.48%)617.7 V119.23 V (17.28%)40686.8 WDrop High
16 mm²76 A59 A45.17 V (6.55%)644.8 V74.52 V (10.8%)25429.2 WDrop High
25 mm²101 A78 A28.91 V (4.19%)661.1 V47.69 V (6.91%)16274.7 WDrop High
35 mm²125 A97 A20.65 V (2.99%)669.3 V34.06 V (4.94%)11624.8 WDrop High
50 mm²151 A118 A14.46 V (2.1%)675.5 V23.85 V (3.46%)8137.4 WDrop High
70 mm²192 A150 A10.33 V (1.5%)679.7 V17.03 V (2.47%)5812.4 WDrop High
95 mm²232 A181 A7.61 V (1.1%)682.4 V12.55 V (1.82%)4282.8 WDrop High
120 mm²269 A210 A6.02 V (0.87%)684.0 V9.94 V (1.44%)3390.6 WDrop High
150 mm²309 A241 A4.82 V (0.7%)685.2 V7.95 V (1.15%)2712.4 WDrop High
185 mm²353 A275 A3.91 V (0.57%)686.1 V6.44 V (0.93%)2199.3 W✓ OK (≤3%)
240 mm²415 A324 A3.01 V (0.44%)687.0 V4.97 V (0.72%)1695.3 W✓ OK (≤3%)
300 mm²477 A372 A2.41 V (0.35%)687.6 V3.97 V (0.58%)1356.2 W✓ OK (≤3%)
400 mm²570 A445 A1.81 V (0.26%)688.2 V2.98 V (0.43%)1017.2 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 60 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 60 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 60m at 690V (voltage drop: 3.91V or 0.57%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.