⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 3.26V (0.47%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.31V (0.48%)
Voltage at Load686.7 VLine Loss: 1832.7 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A401.55 V (58.2%)288.5 V662.37 V (95.99%)226037.5 WDrop High
2.5 mm²24 A18 A240.93 V (34.92%)449.1 V397.42 V (57.6%)135622.5 WDrop High
4 mm²32 A25 A150.58 V (21.82%)539.4 V248.39 V (36.0%)84764.1 WDrop High
6 mm²41 A32 A100.39 V (14.55%)589.6 V165.59 V (24.0%)56509.4 WDrop High
10 mm²57 A44 A60.23 V (8.73%)629.8 V99.35 V (14.4%)33905.6 WDrop High
16 mm²76 A59 A37.65 V (5.46%)652.4 V62.1 V (9.0%)21191.0 WDrop High
25 mm²101 A78 A24.09 V (3.49%)665.9 V39.74 V (5.76%)13562.2 WDrop High
35 mm²125 A97 A17.21 V (2.49%)672.8 V28.39 V (4.11%)9687.3 WDrop High
50 mm²151 A118 A12.05 V (1.75%)678.0 V19.87 V (2.88%)6781.1 WDrop High
70 mm²192 A150 A8.6 V (1.25%)681.4 V14.19 V (2.06%)4843.7 WDrop High
95 mm²232 A181 A6.34 V (0.92%)683.7 V10.46 V (1.52%)3569.0 WDrop High
120 mm²269 A210 A5.02 V (0.73%)685.0 V8.28 V (1.2%)2825.5 WDrop High
150 mm²309 A241 A4.02 V (0.58%)686.0 V6.62 V (0.96%)2260.4 WDrop High
185 mm²353 A275 A3.26 V (0.47%)686.7 V5.37 V (0.78%)1832.7 W✓ OK (≤3%)
240 mm²415 A324 A2.51 V (0.36%)687.5 V4.14 V (0.6%)1412.7 W✓ OK (≤3%)
300 mm²477 A372 A2.01 V (0.29%)688.0 V3.31 V (0.48%)1130.2 W✓ OK (≤3%)
400 mm²570 A445 A1.51 V (0.22%)688.5 V2.48 V (0.36%)847.6 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 50 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 50m at 690V (voltage drop: 3.26V or 0.47%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.