⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

350 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 7.01V (1.69%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 7.13V (1.72%)
Voltage at Load408.0 VLine Loss: 4251.1 W
Max Power & Breaker251.58 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (208.4%)0.0 V1426.63 V (343.77%)524300.0 WDrop High
2.5 mm²24 A18 A518.92 V (125.04%)0.0 V855.98 V (206.26%)314580.0 WDrop High
4 mm²32 A25 A324.33 V (78.15%)90.7 V534.99 V (128.91%)196612.5 WDrop High
6 mm²41 A32 A216.22 V (52.1%)198.8 V356.66 V (85.94%)131075.0 WDrop High
10 mm²57 A44 A129.73 V (31.26%)285.3 V213.99 V (51.57%)78645.0 WDrop High
16 mm²76 A59 A81.08 V (19.54%)333.9 V133.75 V (32.23%)49153.1 WDrop High
25 mm²101 A78 A51.89 V (12.5%)363.1 V85.6 V (20.63%)31458.0 WDrop High
35 mm²125 A97 A37.07 V (8.93%)377.9 V61.14 V (14.73%)22470.0 WDrop High
50 mm²151 A118 A25.95 V (6.25%)389.1 V42.8 V (10.31%)15729.0 WDrop High
70 mm²192 A150 A18.53 V (4.47%)396.5 V30.57 V (7.37%)11235.0 WDrop High
95 mm²232 A181 A13.66 V (3.29%)401.3 V22.53 V (5.43%)8278.4 WDrop High
120 mm²269 A210 A10.81 V (2.61%)404.2 V17.83 V (4.3%)6553.7 WDrop High
150 mm²309 A241 A8.65 V (2.08%)406.4 V14.27 V (3.44%)5243.0 WDrop High
185 mm²353 A275 A7.01 V (1.69%)408.0 V11.57 V (2.79%)4251.1 W✓ OK (≤3%)
240 mm²415 A324 A5.41 V (1.3%)409.6 V8.92 V (2.15%)3276.9 W✓ OK (≤3%)
300 mm²477 A372 A4.32 V (1.04%)410.7 V7.13 V (1.72%)2621.5 W✓ OK (≤3%)
400 mm²570 A445 A3.24 V (0.78%)411.8 V5.35 V (1.29%)1966.1 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 350A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 100m at 415V (voltage drop: 7.01V or 1.69%).

What is the power capacity of 350A at 415V?

At unity power factor, 350A at 415V supports 251.58 kW with a standard 350A circuit breaker.