⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

350 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 17.3V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.4V (3.1%)
Voltage at Load672.7 VLine Loss: 10486.0 W
Max Power & Breaker418.29 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3459.48 V (501.37%)0.0 V5706.53 V (827.03%)2097200.0 WDrop High
2.5 mm²24 A18 A2075.69 V (300.82%)0.0 V3423.92 V (496.22%)1258320.0 WDrop High
4 mm²32 A25 A1297.31 V (188.02%)0.0 V2139.95 V (310.14%)786450.0 WDrop High
6 mm²41 A32 A864.87 V (125.34%)0.0 V1426.63 V (206.76%)524300.0 WDrop High
10 mm²57 A44 A518.92 V (75.21%)171.1 V855.98 V (124.06%)314580.0 WDrop High
16 mm²76 A59 A324.33 V (47.0%)365.7 V534.99 V (77.53%)196612.5 WDrop High
25 mm²101 A78 A207.57 V (30.08%)482.4 V342.39 V (49.62%)125832.0 WDrop High
35 mm²125 A97 A148.26 V (21.49%)541.7 V244.57 V (35.44%)89880.0 WDrop High
50 mm²151 A118 A103.78 V (15.04%)586.2 V171.2 V (24.81%)62916.0 WDrop High
70 mm²192 A150 A74.13 V (10.74%)615.9 V122.28 V (17.72%)44940.0 WDrop High
95 mm²232 A181 A54.62 V (7.92%)635.4 V90.1 V (13.06%)33113.7 WDrop High
120 mm²269 A210 A43.24 V (6.27%)646.8 V71.33 V (10.34%)26215.0 WDrop High
150 mm²309 A241 A34.59 V (5.01%)655.4 V57.07 V (8.27%)20972.0 WDrop High
185 mm²353 A275 A28.05 V (4.07%)662.0 V46.27 V (6.71%)17004.3 W~ ≤5%
240 mm²415 A324 A21.62 V (3.13%)668.4 V35.67 V (5.17%)13107.5 W~ ≤5%
300 mm²477 A372 A17.3 V (2.51%)672.7 V28.53 V (4.14%)10486.0 W✓ OK (≤3%)
400 mm²570 A445 A12.97 V (1.88%)677.0 V21.4 V (3.1%)7864.5 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 350A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 350A over 400m at 690V (voltage drop: 17.3V or 2.51%).

What is the power capacity of 350A at 690V?

At unity power factor, 350A at 690V supports 418.29 kW with a standard 350A circuit breaker.